Parameters
vacon • 109
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
7.1.7
Group 3.6: Fieldbus DataMap
Fieldbus process data out
Default values for Process Data Out to monitor through fieldbus are listed in Table 83.
Example:
Value ‘2500’ for
Output Frequency
corresponds to ‘25.00 Hz’ (scaling value is 0.01).
All monitoring values listed in chapter 6 are given the scaling value.
Table 82. Fieldbus data mapping
Code
Parameter
Min
Max
Unit
Default
ID
Description
P3.6.1
FB DataOut 1 Sel
0
35000
1
852
Data sent to fieldbus can be chosen
with parameter and monitor value
ID numbers. The data is scaled to
unsigned 16-bit format according to
the format on keypad. E.g. 25.5 on
keypad equals 255.
P3.6.2
FB DataOut 2 Sel
0
35000
2
853
Select Process Data Out with
parameter ID
P3.6.3
FB DataOut 3 Sel
0
35000
3
854
Select Process Data Out with
parameter ID
P3.6.4
FB DataOut 4 Sel
0
35000
4
855
Select Process Data Out with
parameter ID
P3.6.5
FB DataOut 5 Sel
0
35000
5
856
Select Process Data Out with
parameter ID
P3.6.6
FB DataOut 6 Sel
0
35000
6
857
Select Process Data Out with
parameter ID
P3.6.7
FB DataOut 7 Sel
0
35000
7
858
Select Process Data Out with
parameter ID
P3.6.8
FB DataOut 8 Sel
0
35000
37
859
Select Process Data Out with
parameter ID
Table 83. Fieldbus Process Data Out
Data
Value
Scale
Process Data Out 1
Output frequency
0.01 Hz
Process Data Out 2
Motor speed
1 rpm
Process Data Out 3
Motor current
0.1 A
Process Data Out 4
Motor torque
0.1%
Process Data Out 5
Motor power
0.1%
Process Data Out 6
Motor voltage
0.1 V
Process Data Out 7
DC-link voltage
1 V
Process Data Out 8
Last active fault code
1