Startup
vacon • 45
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
4.2.6
Multi-purpose application
You can use the Multi-purpose application for different processes (for example conveyors) where a
wide range of motor control functions is necessary.
It is possible to control the drive from the keypad, Fieldbus or I/O terminal. When you use I/O ter-
minal control, the start/stop commands are given through DI1 and DI2, and the frequency reference
from AI1 or AI2.
There are 2 acceleration/deceleration ramps available. The selection between Ramp1 and Ramp2
is made by DI6.
It is possible to configure all the drive outputs freely in all the applications. There are 1 analogue
output (Output Frequency) and 3 relay outputs (Run, Fault, Ready) available on the basic I/O board.
4.2.6.1
M1.35 Multi-purpose
Table 19. Multi-purpose start-up wizard menu
Code
Parameter
Min
Max
Unit
Default
ID
Description
P1.35.1
Control mode
0
1
0
600
0 = U/f Freq ctrl open loop
1 = Speed control open loop
P1.35.2
Auto TorqueBoost
0
1
0
109
Automatic torque boost can
be used in application where
starting torque due to start-
ing friction is high.
0= Disabled
1= Enabled
P1.35.3
Start Acceleration
Time
0.1
3000.0
s
2.0
502
Start Acceleration Time
P1.35.5
Preset Freq 1
P1.3
P1.4
Hz
10.0
105
Preset Frequency 1
P1.35.6
U/f ratio
0
2
0
108
Type of U/f curve between
zero frequency and the field
weakening point.
0=Linear
1=Squared
2=Programmable
P1.35.7
Field WeakngPnt
8.00
P3.3.1.2
Hz
Varies
602
The field weakening point is
the output frequency at
which the output voltage
reaches the field weakening
point voltage
P1.35.8
Voltage at FWP
10.00
200.00
%
100.00
603
Voltage at field weakening
point in % of motor nominal
voltage
P1.35.9
U/f Mid Freq
0.00
P3.1.4.2
Hz
Varies
604
Provided that the program-
mable U/f curve has been
selected (par. P3.1.4.1) , this
parameter defines the mid-
dle point frequency of the
curve.
P1.35.10
U/f Mid Voltg
0.0
100.0
%
100.0
605
Provided that the program-
mable U/f curve has been
selected (par. P3.1.4.1), this
parameter defines the mid-
dle point voltage of the
curve.