Parameters
vacon • 117
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
7.1.10.7
Group 3.9.8: AI Low Protection
7.1.10.8
Group 3.9.9: User Defined Fault 1
7.1.10.9
Group 3.9.10: User Defined Fault 2
Table 92. AI Low Protection settings
Code
Parameter
Min
Max
Unit
Default
ID
Description
P3.9.8.1
AI Low Protection
0
2
2
767
This parameter defines if the AI
Low protection is enabled or dis-
abled.
0 = Disabled
1 = Enabled in Run State
2 = Enabled in Run&Stop States
P3.9.8.2
AI Low Fault
0
5
0
700
Response when an analogue sig-
nal in use goes below 50% of the
minimum signal range. 0 = No
action
1 = Alarm
2 = Alarm, Preset Freq
3 = Alarm, Previous Freq
4= Fault (Stop according to stop
mode)
5 = Fault (Stop by coasting)
Table 93. User Defined Fault 1 settings
Code
Parameter
Min
Max
Unit
Default
ID
Description
P3.9.9.1
User Defined Fault 1
DigIN
Slot0.1
1552
3
Digital input selection for activat-
ing User Defined Fault (1 or 2)
P3.9.9.2
UserDef. Fault1 Resp.
0
3
3
1552
5
0 = No action
1 = Alarm
2 = Fault (Stop according to stop
mode)
3 = Fault (Stop by coasting)
Table 94. User Defined Fault 2 settings
Code
Parameter
Min
Max
Unit
Default
ID
Description
P3.9.10.1
User Defined Fault 2
DigIN
Slot0.1
1552
4
Digital input selection for activat-
ing User Defined Fault (1 or 2)
P3.9.10.2
UserDef. Fault2 Resp.
0
3
3
1552
6
0 = No action
1 = Alarm
2 = Fault (Stop according to stop
mode)
3 = Fault (Stop by coasting)