vacon • 190
Faults
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
57
1057
Identification
Identification run has failed.
Check that motor is connected
to the drive.
Ensure that there is no load on
the motor shaft.
Ensure that the start command
will not be removed before
completion of identification run.
58
1058
Mechanical brake
Actual status of mechanical brake
remains different from the control sig-
nal for longer than what is defined.
Check the status and connec-
tions of the mechanical brake.
60
1060
Low DC Power
The drive has stopped due to insuffi-
cient power from solar panels. The
drive cannot start because DC voltage
is below the threshold level of P14.1.1
or P3.22.1.6.
Check voltage settings and
make sure that acceleration or
deceleration ramps are not too
slow.
61
1061
Restart Delay
The drive will start after the pro-
grammed delay.
63
1063
Low water level
The minimum water level is not ok.
Check settings and water level
status.
64
1064
Max water level
The maximum water level is not ok.
Check settings and water level
status.
65
1065
PC communica-
tion fault
The data connection between the PC
and frequency converter is broken
66
1066
Thermistor fault
The thermistor input has detected an
increase of motor temperature
Check motor cooling and load.
Check thermistor connection
(If thermistor input is not in use
it has to be short circuited)
68
1301
Maintenance
counter 1 alarm
Maintenance counter has reached the
alarm limit.
Carry out the needed mainte-
nance and reset counter.
1302
Maintenance
counter 2 alarm
Maintenance counter has reached the
alarm limit.
Carry out the needed mainte-
nance and reset counter.
1303
Maintenance
counter 3 alarm
Maintenance counter has reached the
alarm limit.
Carry out the needed mainte-
nance and reset counter.
1304
Maintenance
counter 4 alarm
Maintenance counter has reached the
alarm limit.
Carry out the needed mainte-
nance and reset counter.
69
1310
Fieldbus map-
ping error
Non-existing ID number is used for
mapping values to Fieldbus Process
Data Out.
Check parameters in Fieldbus
Data Mapping menu.
1311
Not possible to convert one or more
values for Fieldbus Process Data Out.
The value being mapped may
be of undefined type. Check
parameters in Fieldbus Data
Mapping menu.
1312
Overflow when mapping and converting
values for Fieldbus Process Data Out
(16-bit).
71
1071
Unsupported
The drive is not VACON® 100 X.
1171
Unsupported
The drive has not solar property.
Table 147. Fault codes and descriptions
Fault
code
Fault
ID
Fault name
Possible cause
Remedy