Parameters
vacon • 175
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
7.2.21
Soft fill
P3.13.8.1
E
NABLE
P3.13.8.2
S
OFT
F
ILL
F
REQ
P3.13.8.3
S
OFT
F
ILL
L
EVEL
P3.13.8.4
T
IMEOUT
T
IME
The drive runs at the soft fill frequency (par. P3.13.8.2) until the feedback value reaches the soft fill
level set parameter P3.13.8.3. After this the drive starts to regulate, bump less, from the soft fill
frequency. If the soft fill level is not reached within the timeout (P3.13.8.4) an alarm or fault is trig-
gered (according to the set Soft Fill timeout response (P3.9.1.9)).
Figure 68. Soft fill function
9105.emf
Reference
Soft fill level
Actual value
Soft fill mode
Regulating mode
Frequency
Soft fill frequency