User interfaces
vacon • 73
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
5.3.5.8
Real time clock
5.3.5.9
Power unit settings
Fan control
The fan operates in speed-controlled mode. The speed is controlled according to the drive’s inter-
nal logic that receives data from temperature measurements.
Brake chopper
Sine filter
Table 35. I/O and Hardware menu, Real time clock parameters
Code
Parameter
Min
Max
Unit
Default
ID
Description
V5.5.1
Battery state
1
3
2
2205
Status of battery.
1 = Not installed
2 = Installed
3 = Change battery
P5.5.2
Time
hh:mm:ss
2201 Current time of day
P5.5.3
Date
dd.mm.
2202 Current date
P5.5.4
Year
yyyy
2203 Current year
P5.5.5
Daylight saving
1
4
1
2204
Daylight saving rule
1 = Off
2 = EU; Starts on last Sunday in
March, ends last Sunday in Octo-
ber
3 = US; Start on 2nd Sunday in
March, ends on 1st Sunday in
November
4 = Russia (permanent)
Table 36. Power unit settings, Fan control
Code
Parameter
Min
Max
Unit
Default
ID
Description
V5.6.1.3
Fan stop
0
1
1
826
If enabled, the fan will stop in 5
minutes when the drive is in Ready
state.
0 = Disabled
1 = Enabled
Table 37. Power unit settings, Brake chopper
Code
Parameter
Min
Max
Unit
Default
ID
Description
V5.6.2.1
Brake chopper mode
0
3
0
0 = Disabled
1 = Enabled (Run)
2 = Enabled (Run & Stop)
3 = Enabled (Run, no testing)
Table 38. Power unit settings, Sine filter
Code
Parameter
Min
Max
Unit
Default
ID
Description
V5.6.4.1
Sine filter
0
1
0
0 = Disabled
1 = Enabled