vacon • 104
Parameters
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
7.1.6.3
Group 3.5.2: Analog inputs
NOTE!
The number of usable analogue inputs depends on your (option) board setup. The standard
I/O board embodies 2 analogue inputs.
Group 3.5.2.1: Analog Input 1
Group 3.5.2.2: Analog Input 2
P3.5.1.57
Minimum level logic
Level ok =
input high
1965
Selections for minimum water level logic:
0 = water level is ok when digital input for Minimum
water level is high
1 = water level is ok when digital input for Minimum
water level is low
The drive trips with F63 (Low water level) when water
level is not OK. The fault is reset with autoreset logic of
Under load (see P3.10.5 - 8) when level is restored.
Min level signal/fault refers to level in a well from
which water is taken.
P3.5.1.58
Maximum water level
DigIN Slot0.2
1966 Digital input for maximum water level in the well
P3.5.1.59
Maximum level logic
Level ok =
input high
1967
Selections for maximum water level logic:
0 = water level is ok when digital input for Maximum
water level is high
1 = water level is ok when digital input for Maximum
water level is low
The drive trips with F64 (Max water level) when water
level is not ok. The fault is reset with autoreset logic of
Underload (see P3.10.5 - 8) when level is restored.
Max level signal/fault refers to level in a possible tank
where pumped water is stored.
P3.5.1.60
Dual Supply Enable
DigIN Slot0.2
1991
Digital input high enables relay for the AC switch con-
nection and Dual supply mode logics.
P3.5.1.61
DualS M2Check Disable
DigIN Slot0.1
1989
Digital input high disables the periodic Mode 2 DC volt-
age check, when Dual supply Mode 2 sensorless is
active.
Table 74. Analogue input 1 settings
Code
Parameter
Min
Max
Unit
Default
ID
Description
P3.5.2.1.1
AI1 signal selection
AnIN
SlotA.1
377
Connect the AI1 signal to the ana-
logue input of your choice with this
parameter.
Programmable. See page 91.
P3.5.2.1.2
0.00
300.00
s
0.1
378
Filter time for analogue input.
P3.5.2.1.3
0
1
0
379
0 = 0…10 V / 0…20 mA
1 = 2…10 V / 4…20 mA
P3.5.2.1.4
-160.00
160.00
%
0.00
380
Custom range min setting
20% = 4-20 mA/2-10 V
P3.5.2.1.5
-160.00
160.00
%
100.00
381
Custom range max setting
P3.5.2.1.6
0
1
0
387
0 = Normal
1 = Signal inverted
Table 75. Analogue input 2 settings
Code
Parameter
Min
Max
Unit
Default
ID
Description
P3.5.2.2.1
AI2 signal selection
AnIN
SlotA.2
388
See P3.5.2.1.1.