Group 3.3.3: Preset Freqs
P3.3.1.8
Keypad Reference
0.00
Hz
0.00
184
The frequency reference can be
adjusted on the keypad with this
parameter.
P3.3.1.9
Keypad Direction
0
1
0
123
Motor rotation when control place
is keypad
0 = Forward
1 = Reverse
P3.3.1.10
Fieldbus Ref Sel
1
9
3
122
Selection of ref source when con-
trol place is Fieldbus:
1 = Preset Frequency 0
2 = Keypad reference
3 = Fieldbus
4 = AI1
5 = AI2
6 = AI1+AI2
7 = PID reference
8 = Motor potentiometer
9 = Max Power
P3.3.1.11
Adapt To AC Volt.
No
Yes
No
1931
Parameter enables the possible
limitation on maximum output fre-
quency when connected to AC
mains (digital input from P3.5.1.53
is active), in case the available
voltage is not sufficient to reach
the motor nominal U/f ratio (from
P3.1.1.1 and P3.1.1.2).
The function can be useful if the
motor has been chosen depending
on high DC voltage from solar
modules, but this voltage is not
reachable with AC supply.
Table 66. Preset frequencies parameters
Code
Parameter
Min
Max
Unit
Default
ID
Description
P3.3.3.1
0
1
0
182
0 = Binary coded
1 = Number of inputs. Preset fre-
quency is selected according to how
many of preset speed digital inputs
are active
P3.3.3.2
Hz
5.00
180
Basic preset frequency 0 when
selected by Control reference
parameter (P3.3.1.5).
P3.3.3.3
Hz
10.00
105
Select with digital input:
Preset frequency selection 0
(P3.3.3.10)
P3.3.3.4
Hz
15.00
106
Select with digital input:
Preset frequency selection 1 (P3.3.3.11)
P3.3.3.5
Hz
20.00
126
Select with digital inputs: Preset fre-
quency selection 0 & 1
P3.3.3.6
Hz
25.00
127
Select with digital input:
Preset frequency selection 2 (P3.3.3.12)