6.SETTING AND ADJUSTMENT OF READING
87
6-9-3. Feed rate over asc.
Use this parameter to stop the system if has carried excess feed over a period longer
than specified by this parameter. If the “feed rate over” condition continued longer than
the value specified by FEED RATE OVER ASC., the system is forced to come to a
halt, indicating “Sequence error 7”.
* Setting this parameter to 999 sec disables auto stop function. Over-scale alarm is
displayed.
* Setting this parameter to 0 sec disables auto stop function. Over-scale alarm is not
displayed.
Operation
6-9-4. Load ratio over asc.
Use this parameter to stop the system if has carried excess load ratio over a period
longer than specified by this parameter. If the “load ratio over” condition continued
longer than the value specified by LOAD RATIO OVER ASC., the system is forced to
come to a halt, indicating “Sequence error 8”.
* Setting this parameter to 999 sec disables auto stop function. Over-scale alarm is
displayed.
* Setting this parameter to 0 sec disables auto stop function. Over-scale alarm is not
displayed.
Operation
Range: 0 – 999 sec (3 digits, no decimal place)
MODE
STATES ASCERTAIN
FEED RATE OVER ASC.
→
→
Range: 0 – 999 sec (3 digits, no decimal place)
MODE
STATES ASCERTAIN
LOAD RATE OVER ASC.
→
→