9.OPTION (Option card required)
145
9-3-12. AI zero set
This menu item defines the current/voltage value that corresponds 0.0%. Each channel
can be configured separately. This value has been preset in the factory so that 4.0mA
(0V) input produces 0.0% output. AI zero adjustment should only be carried out when
it is really required.
* Once modified, this parameter cannot be restored to the factory-configured state.
Operation
Enter desired current/voltage value, and press
to confirm.
9-3-13. AI full scale set
This menu item defines the current/voltage value that corresponds 100.0%. Each
channel can be configured separately. This value has been preset in the factory so that
20.0mA (10V) input produces 100.0% output. AI full scale adjustment should only be
carried out when it is really required.
* Once modified, this parameter cannot be restored to the factory-configured state.
Operation
Enter desired current/voltage value, and press
to confirm.
MODE
OPTION
→
PAGE
→
AI ZERO SET
→
→
PAGE
OK
MODE
OPTION
→
PAGE
→
AI FULL SCALE SET
→
PAGE
→
OK