S e c t i o n 5 : P r o g r a m m i n g
45
[301] Panel Events 1
1/2 – Panel AC Fail Trouble/Restore
This reporting code is transmitted when the alarm system AC supply
fails or has been restored. A programmable delay applies to both the
trouble and the restore. This reporting code is sent to the System
Maintenance call direction group.
3/4 – Panel Low Battery Trouble/Restore
These reporting codes are transmitted when the panel battery voltage
falls below 11.5VD or is restored. These reporting codes are sent to
the System Maintenance call direction group.
5/6 – Panel Battery Absent Trouble/Restore
These reporting codes are transmitted when the panel battery voltage
falls below 11.5VD or is restored. These reporting codes are sent to
the System Maintenance call direction group and are transmitted
when the panel battery is detected as absent.
[302] Panel Events 2
1/2 – Bell Circuit Trouble/Restore
This reporting code is transmitted when a bell trouble condition
occurs or is restored on the system.This reporting code is sent to the
System Maintenance call direction group.
3/4 – Telephone Line Trouble and Restore
This reporting code is transmitted when an alarm controller TLM
trouble occurs or is restored. The TLM trouble is communicated over
an unaffected communication path if available.
This reporting code is sent to the System Maintenance call direction
group.
5/6 – Auxiliary Power Supply Trouble/Restore
This reporting code is transmitted when an auxiliary voltage supply
trouble occurs or is restored. This reporting code is sent to the Sys-
tem Maintenance call direction group.
NOTE:
When the electronic fuse built in to the auxiliary power sup-
ply is tripped due to a short or high current draw, the alarm system
must be powered down then back up to reset the fuse.
[305] Panel Events 5
3/4 – PGM 2 2-Wire Trouble/Restore
This reporting code is transmitted when a trouble condition on PGM
2, configured as 2-wire smoke, occurs or is restored. This reporting
code is sent to the System Maintenance call direction group.
[311] Maintenance Events 1
1/2 – RF Jam Trouble/Restore
Sent when RF jam troubles occur/are restored. The following events
cause RF jam troubles:
•
Wireless repeater jamming
•
RF jam
3/4 – Fire Trouble/Restore
Sent when a low sensitivity, tamper or internal fault condition/restore
is detected on a wireless smoke detector.
5 – Cold Start
Sent when power is restored to the alarm system after total power
failure. The code is sent after 2 minutes to allow the alarm controller
to stabilize.
6 – Delinquency
When the Delinquency option is off (page 45), this code is transmit-
ted if the alarm system has not been armed for the number of days
programmed in the Delinquency Transmission Delay (page 48).
When the Delinquency option is on, this code is transmitted when no
zone activity has been detected on the system for the number of hours
programmed in Delinquency Transmission Delay.
[312] Maintenance Events 2
1/2 – Installer Lead In/ Lead Out
The Installer Lead In and Lead Out reporting codes are sent when the
alarm system enters and exits Installer Programming respectively.
When Installer Programming is automatically exited after PC-Link is
activated, the Installer Lead Out event is not communicated until
after the DLS session is complete.
3/4 – DLS Lead In/Lead Out
The DLS Lead In reporting code is sent:
•
after DLS communication has been successfully established, but
before the alarm system calls back the downloading computer.
This code is only transmitted when call back is enabled
•
on user-initiated call-up.
The DLS Lead Out reporting code is sent when a DLS session is suc-
cessfully ended.
NOTE:
If DLS is terminated by an alarm, the DLS Lead Out report-
ing code is not transmitted.
5/6 – SA Lead In/Lead Out
The SA Lead In reporting code is sent:
•
after SA communication has been successfully established, but
before the alarm system calls back the downloading computer.
This code is only transmitted when call back is enabled.
•
on user-initiated call-up.
The SA Lead Out reporting code is sent when an SA session is suc-
cessfully ended. The SA Lead Out reporting code is still sent if the
session is terminated by an alarm.
7 Event Buffer 75% Full
Sent when the event buffer reaches a threshold of 75% without being
uploaded.
[313] Maintenance Events 3
1/2 – Firmware Update Begin/was Successful
Sent when a remote firmware update is initiated/ is successfully com-
pleted.
3 – Firmware Update Fail
Sent after an unsuccessful remote firmware update.
[314] Maintenance Events 4
1/2 – Gas Trouble/Restore
3/4 – Heat Trouble/Restore
5/6 – Freeze Trouble/Restore
7/8 – Probe Disconnected Trouble/Restore
[321] Receiver Events
2/4/6/8 – Receiver 1 - 4 FTC Restore
Sent when the panel detects an FTC trouble.
[331] Module Events 1
1/2 – Module AC Trouble/Restore
This reporting code is transmitted when a module’s AC supply fails
or has been restored. A programmable delay applies to both the trou-
ble and the restore. This reporting code is sent to the System Mainte-
nance call direction group.