S e c t i o n 2 : I n s t a l l a t i o n
8
The Bell output is supervised and power limited by 2A PTC. If
unused, connect a 1000
resistor across Bell+ and Bell- to prevent
the panel from displaying a trouble. See [*][2] on page 17.
2.4.11 Telephone Line Wiring
Wire the telephone connection terminals (TIP, Ring, T-1, R-1) to an
RJ-31x connector as indicated in the following diagram. For connec-
tion of multiple devices to the telephone line, wire in the sequence
indicated. Use 26 AWG wire minimum for wiring.
Diagram 2-14: Telephone Line Wiring
NOTE:
Ensure that all plugs and jacks meet the dimension, tolerance
and metallic plating requirements of 47 C.F.R. Part 68, Sub-Part F. For
proper operation, no other telephone equipment must be connected
between the control panel and the telephone company facilities.
2.4.12 Smoke Detector Wiring
All zones defined as Fire must be wired according to the following
diagram:
Diagram 2-15: Smoke Detector Wiring
See “[001] Zone Type” on page 27
for fire zone operation.
NOTE:
Smoke detectors must be latching type. To reset a smoke detec-
tor, enter [*][7][2].
Table 2-8: Compatible 4-Wire Smoke Detectors
Fire Zone Wiring: 2-wire Smoke Detectors
If PGM 2 is programmed for 2-wire smoke detector
connection, the
detectors must be wired according to the following diagram:
Diagram 2-16: 2-Wire Smoke Detector Wiring
NOTE:
The maximum number of smoke detectors on a 2-wire loop is
18. For more information on Fire zones, see section [001] Zone Type on
page 27.
NOTE:
Do not combine smoke detector models from different manu-
facturers on the same circuit. Operation may be impaired. Refer to the
smoke detector installation sheet when positioning detectors.
Table 2-9: Compatible 2-Wire Smoke Detectors
Table 2-10: 2-Wire Smoke Detector Initiating Circuit
2.4.13 CO Detector
The following hardwired CO detector models can be used with Pow-
erSeries Neo alarm controllers:
•
Potter Model CO-12/24, UL File E321434
•
Quantum Model 12-24SIR, UL File E186246
•
NAPCO Model FW-CO12 or FW-CO1224, UL File E306780
•
System Sensor Model CO1224, UL File E307195
NOTE:
For multiple unit connections, the leads between CO detectors
must be broken. The power supervision relay must be powered from the
last detector in the loop.
Wireless CO detectors are also available. When installing wireless
CO detectors, use only model PG9913
UL
, PG8913, PG4913. An
HSM2HOSTx (x=9
UL
/8/4) wireless receiver or HS2LCDRF(P)x/
HS2ICNRF(P)x (x=9
UL
/8/4) wireless keypad are required when
installing wireless CO detectors. For more details on these wireless
devices, refer to their respective installation manuals.
NOTE:
Use only
UL
approved devices with UL/ULC listed systems.
Table 2-11: CO Detector Ratings
Diagram 2-17: CO Detector Wiring
FSA-410B
FSA-410BLST
FSA-410BRST
FSA-410BT
FSA-410BR
FSA-410BLRST
FSA-410BS
FSA-410BRT
FSA-410BST
FSA-410BRS
Current ratings for DSC FSA-410 Series: 25mA
T-1
R-1
TIP
RING
RJ-31X
RED
GRN
BRN
GRA
To alarm
initiating
circuit
NO C N C
P ane l
EOLR
RM-2
1 PGM 2
COM
+ AUX -
V+
V -
ZONE
Additional 2-wire smoke detectors must be
connected in parallel as shown above.
FSA-210B
FSA-210BLST
FSA-210BRST
FSA-210BT
FSA-210BR
FSA-210BLRST
FSA-210BS
FSA-210BRT
FSA-210BST
FSA-210BRS
Current ratings for DSC FSA-210B series: 35mA
Item
Specification
Style/Class, Supervised, Power Limited
Style B (Class B)
Compatibility Identifier
HS2-1
DC Output Voltage
9.7-13.8 VDC
Detector Load
2mA (MAX)
Single End of Line Resistor (SEOL)
2200
Loop Resistance
24
(MAX)
Standby Impedance
3000
(NOM)
Alarm Impedance
1200
(MAX)
Alarm Current
86mA (MAX)
Device
Description
Max Rating @12V
DC
CO-12/24
Potter model CO detector
40mA
12-24SIR
Quantum model CO detector 75mA
FW-CO12
FW-CO1224
NAPCO model CO detector 90mA
CO DETECTOR
RM-1/RM-2
POWER LOOP
SUPERVISORY
RELAY
(12V
DC
, 35mA)
ALARM
INITIATING
LOOP
RESISTANCE
100 ohm
SEOL
RESISTOR
(5600 ohm)
HS2016/HS2032/HS2064/HS2128