111
4.0.1 UL/ULC Installations
This product has been tested and found in compliance with the following stan-
dards:
UL1610 Central-Station Burglar-Alarm Units
UL365 Police Station Connected Burglar Alarm Units and Systems
UL1023 Household Burglar-Alarm System Units
UL985 Household Fire Warning System Units
UL1635 Digital Alarm Communicator System Units
UL1637 Home Health Care Signaling Equipment
ULC-S304-06Signal Receiving Centre & Premise Burglar Alarm Control Units
ULC-S559-04Equipment for Fire Signal Receiving Centers and Systems
ULC-S545-02 Residential Fire Warning System Control Units
ORD-C1023-1974 Household Burglar-Alarm System Units
This product has also been tested and found in compliance with the ANSI/SIA CP-
01-2010 Control Panel Standard – Features for False Alarm Reduction.
This product is UL/ULC listed under the following categories:
AMCX/AMCXCCentral Stations Alarm Units
APAWPolice-station-connected Alarm Units
DAYRCCentral Station Fire Alarm System Units
UTOU/UTOUC Control Units and Accessories, Household System Type
NBSX/NBSXC Household Burglar Alarm System Units
AMTB Control Panels, SIA False Alarm Reduction
The product is labeled with the UL and ULC listing marks along with the SIA CP-
01 compliance statement (Also Classified in accordance with SIA-CP-01 Standard)
as proof of compliance with the above mentioned standards. For further informa-
tion on this product’s listings please also refer to the official listing guides pub-
lished at the UL web site (www.ul.com) under Online Directions Section.
UL/ULC Residential Fire and Burglary Installations:
For ULC Installations refer to the Standard for the Installation of Residential Fire
Warning Systems, CAN/ULC-S540.
•
All burglary-type zones shall be configured with SEOL or DEOL configura-
tion
(refer to section [002], bit 10 or 11 shall be ON)
•
Use at least one PG9926 or PG9916 Smoke Detector for Fire Installations
(section [001], fire zone shall be programmed as type 025)
•
The entry delay shall not exceed 45 seconds (refer to section [005])
•
The exit delay shall not exceed 60 seconds (refer to section [005])
•
The minimum Bell Time-out is 4 minutes (refer to section [005])
Note:
For ULC Residential Fire Installations the minimum Bell Time-out is 5
minutes
For UL Home Health Care Installations the minimum Bell Time-out is 5 min.
For UL Commercial Burglary Installations minimum Bell Time-out is 15 min.
•
Temporal Three Fire Signal shall be enabled (section [013], opt.8 ON)
•
Arm/Disarm Bell Squawk shall be enabled when using wireless key PG4939,
PG4929, PG4949 (section [014], option 1 shall be ON)
•
A code shall be required for bypassing (section [023], option 4 shall be ON)
•
Trouble beeps shall be enabled (section [022], option 7 shall be ON)
•
AC trouble indication LED shall be enabled (Keypad Programming, section
[022], options 5 and 6 shall be ON)
•
DACT Communicator shall be enabled for Supervising Station Monitoring
(section [380], option 1 shall be ON)
Note:
The DACT communicator for this product has no line security.
•
Telephone Line Monitoring (TLM) shall be enabled (section [015], option 7
shall be ON)
Note:
This product is programmed to perform 5 (min.) to 10 (max.) attempts
for communication of an event to the supervising station. If unsuccessful, a
Fail To Communicate (FTC) trouble is generated.
•
Test transmission cycle shall be set for monthly transmission (refer to section
[351])
Note:
For ULC Residential/Commercial installations set for daily test trans-
mission
•
Wireless Supervision window shall be set to 4 hours for Fire Installations
(Wireless Programming, section [804]>[802] shall be programmed with the
value 16)
•
Wireless Supervision window shall be set to 4 hours for Burglary Installa-
tions only (Wireless Programming, section [804]>[802] shall be programmed
with the value 96)
•
RF Jam detection shall be enabled (refer to Wireless Programming (section
[804][801], option 00 shall be OFF)
•
New Alarms will Disconnect 2-way Audio (section [022], opt 6 OFF)
UL Central Station and Police Connect with Standard or Encrypted Line Secu-
rity Service
•
The installation must use the Models TL2803G(R) IP/3G Interface,
3G2080(R) 3G Interface or TL280(R) IP Interface, which communicates
over Cellular Data Network or an Ethernet network 10/100BaseT to the com-
patible Sur-Gard System I/II/III/IV receiver.
•
Polling time shall be 200 seconds and compromise detection time shall be 6
min.
•
For Encrypted line security applications, the Models TL2803G(R) IP/3G
Interface, 3G2080(R) 3G Interface or TL280(R) IP Interface shall have the
Encryption Key enabled (AES128 bit encryption algorithm is validated
under NIST Certificate No.xxx
•
Wireless Supervision window shall be enabled (refer to Wireless Program-
ming, sections [804]>[802])
UL Local, Central Station and Police Connect with No Line Security Service
•
The installation shall use a Bell which is UL Listed for Mercantile local
alarms. An example of a UL Listed bell that can be used is Amseco Model
MBL10B bell with Model AB-12 bell housing. Connections from the control
unit to the bell shall be made in conduit. (Optional for central Station)
•
The bell timeout shall be programmed for 15 minutes minimum
•
At least one system remote keypad with tamper switch shall be employed
•
The integral DACT shall be enabled and shall be programmed to provide a
low battery transmission
•
The control panel shall be in the attack resistant enclosure. The separately
listed CMC-1 or PC4050CA attack resistant enclosure shall be employed
•
The maximum entry delay time shall not exceed 45s as a result of the attack
test. The maximum exit delay time shall not exceed 60 s.
•
A tamper switch shall be used to protect the enclosure cover of the control
unit. A tamper switch shall also be used on the keypad rear to detect removal
from the wall.
•
24 h check in transmission shall be enabled
•
Open/Closing acknowledgement enabled.(Not Police Station)
•
The Installation shall use the internal dialer (DACT) alone or in conjunction
with Models TL2803G(R) IP/3G Interface, 3G2080(R) 3G Interface or
TL280(R) IP Interface, which communicates over Cellular Data Network or
an Ethernet network 10/100BaseT to the compatible Sur-Gard System I/II/
III/IV receiver.
UL Home Health Care Signaling Equipment
•
There must be at least two keypads, one of either one of the compatible key-
pads models HS2LED, HS2LCD(P), HS2ICN(P), HS2LCDRF(P)9, HS2IC-
NRF(P)9
•
Each system shall be programmed to activate an audible Trouble signal
within 90 seconds upon loss of microprocessor memory
ULC Central Station Fire and Burglary Monitoring Installations
•
For installation requirements, levels of security, communication modules and
configurations (Refer to the ULC Installation Information Sheet, DSC
#29002157)
•
Use a CSA/cUL approved transformer (hardwired connections required for
Fire Monitoring)
•
All tamper circuits may be connected to the same zone
Programming
The notes in the programming sections of the PowerSeries Neo Reference Manual
describing the system configurations for UL/ULC listed installations shall be
implemented.
Control of the Protected Premises
In order to have a UL certificated system, the protected area is to be under the
responsibility of one ownership and management (i.e., one business under one
name). This may be a group of buildings attached or unattached with different
addresses but under the responsibility of someone having mutual interest. The per-
son of mutual interest is not the alarm-installing company.
Note:
This does not apply to strip mall applications where each independent busi-
ness must have their own separate alarm system.
e.g.,1: a commercial partitioned system that has an office and a warehouse area in a
building where each area can be armed or disarmed independently.
e.g.,2: a residential system partitioned so that the garage area is armed separately
from the house.
Each of the above examples is under the sole responsibility of a single owner. The
bell and DACT power supply must be in a protected area including partitioned sys-
tems. The bell and DACT power supply must be located where it can be heard by
the person or persons responsible for maintaining the security system during the
daily arming cycle.
Bell Location
The alarm sounding device (bell) shall be located where it can be heard by the per-
son operating the security system during the daily arming and disarming cycle.
Protection of the Control Unit
The local control unit and the local power supply must be protected in one of the
following ways:
•
The control unit and audible alarm device must be in a protected area which
is armed 24 hours a day.
•
Each partition must arm the area protecting the control unit and the audible
alarm device power supply. This may require duplicate protection armed by
each partition. Access to this protected area, without causing and alarm, will
require that all partitions be disarmed.
•
In all cases described above, the protected area for the control unit must be
programmed as not-bypassable.
Casual Users
The installer should caution the user(s) not to give system information (e.g., codes,
bypass methods, etc.) to casual users (baby-sitters or service people). Only the
One-Time Use codes shall be given to casual users.
User Information
The installer should advise the users and note in the User’s Manual:
•
Service organization name and telephone number
•
The programmed exit time
•
The programmed entry time
•
Test system weekly
•
The installer code cannot arm or disarm the system