Settings
68
Index
Sub-ind
ex
Name
Unit
Setting range
Default
value
effective
Period
0x0C-linear motor;
Byte1, Byte2, Byte3: Reserved
The setting of the motor type must be consistent with the actual drive motor type, otherwise the drive or
motor can be damaged.
Index
Sub-ind
ex
Name
Unit
Setting range
Default
value
effective
Period
0x2059
0
Motor Thermal Time
Constant
sec
60~6000
1100
Restart
Y
Set the motor thermal time constant which is used for detecting motor continuous overload.
Obtain the accurate value of this parameter from the motor manufactuer.
Index
Sub-ind
ex
Name
Unit
Setting range
Default
value
effective
Period
0x205A
0
Motor
Operation
Environment
-
0~0x07010101
0x00010
000
Immediat
ely
Y
Set the operating environment of the motor.
Byte0: Cooling mode
0x00-Natural cooling;
0x01-Forced air cooling.
Byte1: Installation mode
0x00-suspended installation;
0x01-base plate installation.
Byte2: Installation space
0x00-Confined space;
0x01-Open space.
Byte3: heat dissipation level of motor
0x00-Level 0;
0x01-Level 1;
0x02-Level 2;
0x03-Level 3;
0x04-Level 4;
0x05-Level 5;
0x06-Level 6;
The higher the heat dissipation level of the motor is, the higher the heat dissipation capacity of the motor is, that is, the