Maintenance
229
Index
Name
Unit
Setting range
Default value
Effective
Period
0x6066
Excessive
position
following
error detection time
ms
1-10000
50
Immediately
Y
Description:
When the [Excessive position following error threshold] is set to 0, the "excessive position following error" alarm will not be
detected. The unit is determined by 0x6089 and 0x608A. Set this parameter according to the actual encoder resolution.
The [Excessive position following error detection time] is used to set the period of time for judging excessive position following
errors.
Index
Name
Unit
Setting range
Default value
Effective
Period
0x21F7
Second
excessive
position
following error threshold
PosUnit
0-4294967295
262144
Immediately
Y
Description:
When the [Second excessive position following error threshold] is set to 0, the "second excessive position following error"
alarm will not be detected. The unit is determined by 0x6089 and 0x608A. Set this parameter according to the actual encoder
resolution.
As long as the position error exceeds the set value of this parameter, "second excessive position following error" will be
immediately reported. In general, set the value of this parameter to be greater than the [position following error threshold].
Index
Name
Unit
Setting range
Default value
Effective
Period
0x20AA
Motor Instantaneous Overload
Threshold
%
100-500
200
Immediately
Y
0x20AB
Motor Instantaneous Overload
Detection Time
sec
1-100
10
Immediately
Y
Description:
The unit of [Motor Instantaneous Overload Threshold] is one percent of the rated current of motor.
Index
Name
Unit
Setting range
Default value
Effective
Period
0x20AC
Excessive Power- On Position
Error Threshold
PosUnit
0-4294967295
0
Immediately
Y
Description:
This parameter is used to set the threshold of excessive power-on position error. If the set value is 0, whether the position error
is too large will not be checked at power-on. The unit is determined by 0x6089 and 0x608A. Set this parameter according to the
actual encoder resolution.
Index
Name
Unit
Setting range
Default value
Effective
Period
0x20C6
Control
Power
Supply
Under-voltage
Detection
%
50-200
100
Immediately
Y