Adjustment
135
Index
Name
Unit
Setting range
Default value
effective
Period
0x21F7
2
nd
Following Error Window
PosUnit
0-4294967295
262144
Immediately
Y
0x20A3
Velocity following window
rev/min
0-10000
50
Immediately
Y
0x20A4
Velocity following window
time
ms
1-10000
50
Immediately
Y
When the Following Error Window is set to 0, the fault detection of"
Excessive position following error "
is disabled.
When the Velocity following window is set to 0, the fault detection of " Excessive velocity following error
" is disabled.
When the 2
nd
Following Error Window is set to 0, the fault detection of the "2
nd
Excessive position
following error " is disabled.
Current Loop Setting
7.3
Overview
7.3.1
This section introduces the setting method of the related parameters of the current loop regulator. The current loop
control settings are divided into [Auto setting] and [Manual setting].
When [Auto setting] is selected, the setting of the parameter [Current Loop Proportional Gain] (0x2169) and the parameter
[Current Loop Integration Time Constant] (0x216A) are invalid. Only the parameter [Current Control Gain Auto Setting Factor]
(0x21E4) is effective.
When [Manual Setting] is selected, the parameter [Current Loop Proportional Gain] (0x2169) and the parameter [Current
Loop Integration Time Constant] (0x216A) become effective. [Current Control Gain Auto Setting Factor] (0x21E4) is invalid.
Associated parameters
7.3.2
The parameters related to [Auto Setting] are shown in the table below.
Index
Name
Unit
Setting range
Default value
effective
Period
0x21E3
Current Loop Control Setting
—
0-0x00000001
0
Restart
Y
0x21E4
Current Control Gain Auto
Setting Factor
0.001
100-2000
1000
Immediately
Y
The parameters related to [Manual setting] are shown in the table below.
Index
Name
Unit
Setting range
Default value
effective
Period
0x21E3
Current Loop Control Setting
—
0-0x00000001
0
Restart
Y
0x2169
Current Loop Proportional Gain
0.001
1-100000
1200
Immediately
Y
0x216A
Current Loop Integration Time
Constant
μs
1-1000000
2500
Immediately
Y