Bits no. 12-15 are used to transfer parameter com-
mands from master to slave and the slave's pro-
cessed responses back to the master.
Parameter commands masterslave
Bit no.
15 14 13 12 Parameter command
0
0
0
0 No command
0
0
0
1 Read parameter value
0
0
1
0 Write parameter value in RAM
(word)
0
0
1
1 Write parameter value in RAM
(double word)
1
1
0
1 Write parameter value in RAM
and EEprom (double word)
1
1
1
0 Write parameter value in RAM
and EEprom (word)
1
1
1
1 Read/write text
Response slavemaster
Bit no.
Response
15 14 13 12
0
0
0
0 No response
0
0
0
1 Parameter value transferred
(word)
0
0
1
0 Parameter value transferred
(double word)
0
1
1
1 Command cannot be performed
1
1
1
1 Text transferred
If the command cannot be performed the slave sends
this response: 0111
Command cannot be performed
and gives the following fault report in the parameter
value (PWE):
Response
(0111)
Fault report
0
The parameter number used does
not exist
1
There is no write access to the de-
fined parameter
2
Data value exceeds the parame-
ter's limits
3
The sub index used does not exist
4
The parameter is not the array type
5
The data type does not match the
defined parameter
17
Data change in the defined param-
eter is not possible in the frequency
converter's present mode. Certain
parameters can only be changed
when the motor is turned off
130
There is no bus access to the de-
fined parameter
131
Data change is not possible be-
cause factory Setup is selected
58
TR1
2800
Series
VFD
Programming
Содержание VarioTrane TR1 2800 Series
Страница 2: ...T TR R1 1 2 28 80 00 0 S Se er ri ie es s V VF FD D 1 1...
Страница 3: ...2 2 T TR R1 1 2 28 80 00 0 S Se er ri ie es s V VF FD D...
Страница 4: ...TR1 2800 Series VFD 3...
Страница 7: ...6 TR1 2800 Series VFD...
Страница 87: ...Illustration 5 7 192H4719 Illustration 5 8 192H4720 86 TR1 2800 Series VFD...
Страница 95: ...Branch Circuit Protection Short circuit protection 94 TR1 2800 Series VFD...
Страница 107: ...All about TR1 2800 Series VFD 106 TR1 2800 Series VFD...