411
Switching frequency
Value:
3000 - 14000 Hz (TR1 2803 - 2875)
4500 Hz
3000 - 10000 Hz (TR1 2880 - 2882)
4500 Hz
Function:
The set value determines the switching frequency of
the inverter. If the switching frequency is changed,
this may help to minimise possible acoustic noise
from the motor.
NOTE:
The output frequency of the frequency converter can
never assume a value higher than 1/10 of the switch-
ing frequency.
Description of choice:
When the motor is running, the switching frequency
is adjusted in parameter 411
Switching frequency
until
the frequency has been obtained at which the motor
is as low-noise as possible.
NOTE:
The switching frequency is reduced automatically as
a function of the load. See
Temperature-Dependent
Switching Frequency
under
Special Conditions
.
When
LC-filter connected
is selected in parameter 412,
the minimum switching frequency is 4.5 kHz.
412
Variable switching frequency
Value:
Without LC-filter (WITHOUT LC-FILTER)
[2]
LC-filter connected
(LC-filter
connected)
[3]
Function:
The parameter must be set to
LC-filter connected
if an
LC-filter is connected between the adjustable fre-
quency drive and the motor.
Description of choice:
The LC-filter connected
[3] must be used if an LC-filter
is connected between the adjustable frequency drive
and the motor, as otherwise the adjustable frequency
drive cannot protect the LC-filter.
NOTE:
When the LC filter is selected the switching frequency
is changed to 4.5 kHz.
413
Overmodulation f unction
Value:
Off
(off)
[0]
On
(on)
[1]
Function:
This parameter allows connection of the overmodu-
lation function for the output voltage.
Description of choice:
Off
[0] means that there is no overmodulation of the
output voltage, which means that torque ripple on the
motor shaft is avoided. This can be a good feature,
e.g. on grinding machines.
On
[1] means that an output voltage can be obtained
which is greater than the mains voltage (up to 5 %).
414
Minimum feedback, FB MIN
Value:
-100,000.000 - par. 415 FBMAX
0.000
Function:
Parameter 414
Minimum feedback, FB MIN
and 415
Maximum feedback, FB MAX
are used to scale the dis-
play text to make it show the feedback signal in a
process unit proportionally to the signal on the input.
Description of choice:
Set the value to be shown on the display as the min-
imum feedback signal value on the selected feedback
input (parameters 308/314
Analogue inputs
).
415
Maximum feedback, FBMAX
Value:
FBMIN - 100,000.000
100
Function:
See description of parameter 414
Minimum feedback,
FB MIN
.
Description of choice:
Set the value to be shown on the display when the
maximum feedback has been obtained on the selec-
ted feedback input (parameter 308/314
Analogue in-
puts
).
416
Process units
Value:
No
unit
(No
unit)
[0]
%
(%)
[1]
ppm
(ppm)
[2]
rpm
(rpm)
[3]
bar
(bar)
[4]
Cycles/min
(CYCLE/MI)
[5]
Pulses/s
(PULSE/S)
[6]
Units/s
(UNITS/S)
[7]
Units/min.
(UNITS/MI)
[8]
Units/h
(Units/h)
[9]
°
C
(°C)
[10]
Pa
(pa)
[11]
l/s
(l/s)
[12]
m3 /s (m3/s)
[13]
l/min.
(l/m)
[14]
m3 /min. (m3/min)
[15]
l/h
(l/h)
[16]
m3 /h (m3/h)
[17]
Kg/s
(kg/s)
[18]
Kg/min.
(kg/min)
[19]
Kg/hour
(kg/h)
[20]
48
TR1
2800
Series
VFD
Programming
Содержание VarioTrane TR1 2800 Series
Страница 2: ...T TR R1 1 2 28 80 00 0 S Se er ri ie es s V VF FD D 1 1...
Страница 3: ...2 2 T TR R1 1 2 28 80 00 0 S Se er ri ie es s V VF FD D...
Страница 4: ...TR1 2800 Series VFD 3...
Страница 7: ...6 TR1 2800 Series VFD...
Страница 87: ...Illustration 5 7 192H4719 Illustration 5 8 192H4720 86 TR1 2800 Series VFD...
Страница 95: ...Branch Circuit Protection Short circuit protection 94 TR1 2800 Series VFD...
Страница 107: ...All about TR1 2800 Series VFD 106 TR1 2800 Series VFD...