500
Address
Value:
Parameter 500 Protocol = FC protocol [0]
0
-
247
1
Parameter 500 Protocol = Metasys N2 [1]
1 - 255
1
Parameter 500 Protocol = MODBUS RTU [3]
1
-
247
1
Function:
This parameter allows the allocation of an address to
each frequency converter in a serial communication
network.
Description of choice:
The individual frequency converter must be allocated
a unique address.
If the number of units connected (frequency convert-
ers + master) is higher than 31, a repeater must be
used.
Parameter 500
Address
cannot be selected via the se-
rial communication, but must be preset via the con-
trol unit.
501
Baudrate
Value:
300
Baud
(300
BAUD)
[0]
600
Baud
(600
BAUD)
[1]
1200
Baud
(1200
BAUD)
[2]
2400
Baud
(2400
BAUD)
[3]
4800
Baud
(4800
BAUD)
[4]
9600
Baud
(9600
BAUD)
[5]
Function:
This parameter is for programming the speed at
which data is transmitted via the serial port. Baud rate
is defined as the number of bits transmitted per sec-
ond.
Description of choice:
The frequency converter's transmission speed must
be set at a value corresponding to the transmission
speed of the master.
Parameter 501
Baudrate
cannot be selected via the
serial port, but must be preset via the operating unit.
502
Coasting Stop
Value:
Digital input (DIGITAL INPUT)
[0]
Serial port (SERIAL PORT)
[1]
Logic
and
(LOGIC
AND)
[2]
Logic
or
(LOGIC
OR)
[3]
Function:
Parameters 502-508 allow a choice between control-
ling the adjustable frequency drive via the digital
inputs and/or via the serial port.
If
Serial port
[1] is selected, the relevant command can
only be activated if a command is given via the serial
port.
In the case of
Logic and
[2] the function must also be
activated via a digital input.
Description of choice:
The table below shows when the motor is running
and when it is coasting, when each of the following
is selected:
Digital input
[0],
Serial port
[1],
Logic and
[2] or
Logic or
[3].
Digital input
[0]
Dig. input
Ser. port
Function
0
0
Coasting
0
1
Coasting
1
0
Motor
running
1
1
Motor
running
Serial port
[1]
Dig. input
Ser. port
Function
0
0
Coasting
0
1
Motor
running
1
0
Coasting
1
1
Motor
running
Logic and
[2]
Dig. input
Ser. port
Function
0
0
Coasting
0
1
Motor
running
1
0
Motor
running
1
1
Motor
running
Logic or
[3]
Dig. input
Ser. port
Function
0
0
Coasting
0
1
Coasting
1
0
Coasting
1
1
Motor
running
TR1
2800
Series
VFD
71
Serial Communication
NOTICE
Note that
Coasting stop
and Bit 03 in the control word
are active at logic '0'.
Programming
Содержание VarioTrane TR1 2800 Series
Страница 2: ...T TR R1 1 2 28 80 00 0 S Se er ri ie es s V VF FD D 1 1...
Страница 3: ...2 2 T TR R1 1 2 28 80 00 0 S Se er ri ie es s V VF FD D...
Страница 4: ...TR1 2800 Series VFD 3...
Страница 7: ...6 TR1 2800 Series VFD...
Страница 87: ...Illustration 5 7 192H4719 Illustration 5 8 192H4720 86 TR1 2800 Series VFD...
Страница 95: ...Branch Circuit Protection Short circuit protection 94 TR1 2800 Series VFD...
Страница 107: ...All about TR1 2800 Series VFD 106 TR1 2800 Series VFD...