percentage value set in parameter 219
Catch-up/Slow-
down reference
.
Slow-down Catch-up
Function
0
0
Unchanged
speed
0
1
Increase by % value
1
0
Reduce
by
%
value
1
1
Reduce
by
%
value
Ramp 2
is selected if a shift between ramp 1 (param-
eters 207-208) and ramp 2 (parameters 209-210) is
required. Logic '0' leads to ramp 1 and logic '1' leads
to ramp 2.
Preset reference, lsb
and
Preset reference, msb
makes
it possible to select one of the four preset references,
see the table below:
Preset ref.
msb
Preset ref.
lsb
Function
0
0
Preset
ref.
1
0
1
Preset
ref.
2
1
0
Preset
ref.
3
1
1
Preset
ref.
4
Preset reference on
is used for shifting between re-
mote-controlled reference and preset reference. It is
assumed that External/preset [2] has been selected in
parameter 214
Reference function
. Logic '0' = remote-
controlled references are active, logic '1' = one of the
four preset references is active, as can be seen from
the table above.
Thermistor
is to be selected if a possibly integrated
thermistor in the motor is to be able to stop the fre-
quency converter if the motor overheats. The cut-out
value is 3 k
Ω
.
If a motor features a Klixon thermal switch instead,
this can also be connected to the input. If motors op-
erate in parallel, the thermistors/thermal switches
can be connected in series (total resistance lower
than 3 k
Ω
).
Parameter 128
Motor thermal protection
must be pro-
grammed for
Thermistor warning
[1] or
Thermistor
trip
[2] and the thermistor is to be connected between
a digital input and terminal 50 (+ 10 V supply).
Precise stop, inverse
is selected to obtain a high degree
of accuracy when a stop command is repeated. A
logic 0 means that the motor speed is ramped down
to stop via the selected ramp.
Precise start/stop
is selected to obtain a high degree
of accuracy when a start and stop command is re-
peated.
Pulse reference
is selected if the reference signal ap-
plied is a pulse train (frequency). 0 Hz corresponds to
parameter 204
Minimum reference, Ref MIN
. The fre-
quency set in parameter 327
Pulse reference/feed-
back
corresponds to parameter 205
Maximum refer-
ence Ref MAX
.
Pulse feedback
is selected if the feedback signal used
is a pulse train (frequency). In parameter 327
Pulse
reference/feedback
the maximum pulse feedback fre-
quency is set.
Pulse input
is selected if a specific number of pulses
must lead to a
Precise stop
, see parameter 343
Precise
stop
and parameter 344
Counter value
.
Selection of Setup, lsb
and
Selection of Setup, msb
gives
the possibility to select one of the four setups. It is,
however, a condition that parameter 004 is set to
Multisetup
.
Reset and start
can be used as a start function. If 24 V
are connected to the digital input, this will cause the
frequency converter to reset and the motor will ramp
up to the preset reference.
Pulse counter start
is used to start a counter stop se-
quence with a pulse signal. The pulse width must at
least be 14 ms and not longer than the count period.
See also parameter 343 and the instruction,
MI28CXYY.
TR1
2800
Series
VFD
41
Programming
Содержание VarioTrane TR1 2800 Series
Страница 2: ...T TR R1 1 2 28 80 00 0 S Se er ri ie es s V VF FD D 1 1...
Страница 3: ...2 2 T TR R1 1 2 28 80 00 0 S Se er ri ie es s V VF FD D...
Страница 4: ...TR1 2800 Series VFD 3...
Страница 7: ...6 TR1 2800 Series VFD...
Страница 87: ...Illustration 5 7 192H4719 Illustration 5 8 192H4720 86 TR1 2800 Series VFD...
Страница 95: ...Branch Circuit Protection Short circuit protection 94 TR1 2800 Series VFD...
Страница 107: ...All about TR1 2800 Series VFD 106 TR1 2800 Series VFD...