Example - Reading a parameter value:
The value in parameter 207
Ramp up time 1
is re-
quired.
The master sends the following request:
PKE = 10CF Hex - read parameter 207
Ramp up
time 1
IND = 0000 Hex
PWEHIGH = 0000 Hex
PWELOW = 0000 Hex
If the
value in parameter 207
Ramp-up time 1
is 10 sec., the
response from the slave to the master will be:
Conversion:
Under the section entitled
Factory Settings
the various
attributes of each parameter are displayed. As a pa-
rameter value can only be transferred as a whole
number, a conversion factor must be used to transfer
decimals.
Example:
Parameter 201
Output frequency, low limit f MIN
has a
conversion factor of 0.1. If you wish to preset the
minimum frequency to 10 Hz, the value 100 must be
transferred, as a conversion factor of 0.1 means that
the value transferred is multiplied by 0.1. The value
100 will thus be perceived as 10.0.
Conversion table
Conversion
index
Conversion
factor
73
0.1
2
100
1
10
0
1
-1
0.1
-2
0.01
-3
0.001
-4
0.0001
-5
0.00001
TR1
2800
Series
VFD
61
Programming
Содержание VarioTrane TR1 2800 Series
Страница 2: ...T TR R1 1 2 28 80 00 0 S Se er ri ie es s V VF FD D 1 1...
Страница 3: ...2 2 T TR R1 1 2 28 80 00 0 S Se er ri ie es s V VF FD D...
Страница 4: ...TR1 2800 Series VFD 3...
Страница 7: ...6 TR1 2800 Series VFD...
Страница 87: ...Illustration 5 7 192H4719 Illustration 5 8 192H4720 86 TR1 2800 Series VFD...
Страница 95: ...Branch Circuit Protection Short circuit protection 94 TR1 2800 Series VFD...
Страница 107: ...All about TR1 2800 Series VFD 106 TR1 2800 Series VFD...