Programming
001
Language
Value:
English
(english)
[0]
German
(deutsch)
[1]
French
(francais)
[2]
Danish
(dansk)
[3]
Spanish
(espanol)
[4]
Italian
(italiano)
[5]
Function:
This parameter is used to choose the language to be
shown in the display whenever the LCP control unit
is connected.
Description of choice:
There is a choice of the languages shown. The factory
setting may vary.
002
Value:
Remote operation (REMOTE)
[0]
Local operation (LOCAL)
[1]
Function:
There is a choice of two different modes of operation
of the adjustable frequency drive;
Remote operation
[0] or
Local operation
[1]. See also parameter 013
Local
control
if
Local operation
[1] is selected.
Description of choice:
If
Remote operation
[0] is selected, the adjustable fre-
quency drive is controlled via:
1.
the control terminals or via serial communica-
tion.
2.
the [START] key. This cannot, however, override
stop commands transmitted via the digital inputs
or via serial communication.
3.
the [STOP/RESET] and [JOG] keys, on the condi-
tion that these are active.
If
Local operation
[1], is selected, the adjustable fre-
quency drive is controlled via:
1.
the [START] key. This cannot, however, override
stop commands via the digital inputs (see pa-
rameter 013
Local control
).
2.
the [STOP/RESET] and [JOG] keys, on the condi-
tion that these are active.
3.
the [FWD/REV] key, on the condition that is has
been selected as active in parameter 016
Local
reversing
, and that parameter 013
Local control
is
set at
Local control and open loop
[1] or
Local control
as parameter 100
[3]. Parameter 200
Output fre-
quency range
is set at
Both directions
.
4.
parameter 003
Local reference
where the refer-
ence can be set using the [+] and [-] keys.
5.
an external control command that can be con-
nected to the digital inputs (see parameter 013
Local control
).
NOTE:
The [JOG] and [FWD/REV] keys are located on the LCP
control unit.
003
Local reference
Value:
Par. 013
Local control
must be set to [1]
or [2]:
0 - f MAX (par. 205)
50 Hz
Par. 013
Local control
must be set to [3] or
[4].
Ref MIN - Ref MAX (par. 204-205)
0,0
Function:
In this parameter, the local reference can be set man-
ually. The unit of the local reference depends on the
configuration selected in parameter 100
Configura-
tion
.
Description of choice:
In order to protect the local reference, parameter 002
Local/remote operation
must be set to
Local operation
[1]. Local reference cannot be set via serial commu-
nication.
TR1
2800
Series
VFD
17
Operation Display
Содержание VarioTrane TR1 2800 Series
Страница 2: ...T TR R1 1 2 28 80 00 0 S Se er ri ie es s V VF FD D 1 1...
Страница 3: ...2 2 T TR R1 1 2 28 80 00 0 S Se er ri ie es s V VF FD D...
Страница 4: ...TR1 2800 Series VFD 3...
Страница 7: ...6 TR1 2800 Series VFD...
Страница 87: ...Illustration 5 7 192H4719 Illustration 5 8 192H4720 86 TR1 2800 Series VFD...
Страница 95: ...Branch Circuit Protection Short circuit protection 94 TR1 2800 Series VFD...
Страница 107: ...All about TR1 2800 Series VFD 106 TR1 2800 Series VFD...