The dip switch is only on the control card with Profi-
bus DP communication.
The switch position shown is the factory setting.
Switches 1 and 2 are used as cable termination for
the RS 485 interface. If the frequency converter is lo-
cated as the first or last unit in the bus SYSTEM,
switches 1 and 2 must be ON. On the remaining fre-
quency converters, switches 1 and 2 must be OFF.
Switches 3 and 4 are not applied.
Connection to terminals 68-70 or
Sub D:
-
PIN 3 GND
-
PIN 8 P-RS 485
-
PIN 9 N-RS 485
An LCP 2 control unit can be connected to the Sub D
plug on the control card. Ordering number:
175N0131.
LCP control unit with ordering number 175Z0401 is
not to be connected.
TR1
2800
Series
VFD
103
Switches 1-4
TR1 2800 Software Dialog
Sub D Plug
Electrical Installation