Frequency converter address (ADR)
Two different address formats are used, with the fre-
quency converter's address range being either 1-31
or 1-126.
1. Address format 1-31
The byte for address range 1-31 has the following
profile:
Bit 7 = 0 (address format 1-31 active)
Bit 6 is not used
Bit 5 = 1: Broadcast, address bits (0-4) are not
used
Bit 5 = 0: No Broadcast
Bit 0-4 = Frequency converter address 1-31
2. Address format 1-126
The byte for address range 1 - 126 has the following
profile:
Bit 7 = 1 (address format 1-126 active)
Bit 0-6 = Frequency converter address 1-126
Bit 0-6 = 0 Broadcast
The slave sends the address byte back unchanged in
the response telegram to the master.
Example:
writing to frequency converter address 22 (16H) with
address format 1-31:
Data control byte (BCC)
The data control byte is explained in this example:
Before the first byte in the telegram is received, the
Calculated CheckSum (BCS) is 0.
When the first byte (02H) has been received:
BCS = BCC EXOR “first byte”
(EXOR = exclusive-or)
Each subsequent byte gates with BCS EXOR and pro-
duces a new BCC, e.g.:
BCS
= 0 0 0 0 0 0 1 0 (02H)
EXOR
2nd byte
= 1 1 0 1 0 1 1 0 (D6H)
BCC
= 1 1 0 1 0 1 0 0 (D4H)
56
TR1
2800
Series
VFD
Programming
Содержание VarioTrane TR1 2800 Series
Страница 2: ...T TR R1 1 2 28 80 00 0 S Se er ri ie es s V VF FD D 1 1...
Страница 3: ...2 2 T TR R1 1 2 28 80 00 0 S Se er ri ie es s V VF FD D...
Страница 4: ...TR1 2800 Series VFD 3...
Страница 7: ...6 TR1 2800 Series VFD...
Страница 87: ...Illustration 5 7 192H4719 Illustration 5 8 192H4720 86 TR1 2800 Series VFD...
Страница 95: ...Branch Circuit Protection Short circuit protection 94 TR1 2800 Series VFD...
Страница 107: ...All about TR1 2800 Series VFD 106 TR1 2800 Series VFD...