100
Configuration
Value:
Speed control, open loop
(SPEED
OPEN
LOOP)
[0]
Speed control, closed loop
(SPEED
CLOSED
LOOP)
[1]
Process control, closed loop
(PROCESS CLOSED LOOP)
[3]
Function:
This parameter is used to select the configuration to
which the frequency converter is to be adapted. This
makes adaptation to a given application simple, since
the parameters not used in a given configuration are
hidden (not active).
Description of choice:
If
Speed control, open loop
[0] is selected, normal
speed control is obtained (without feedback signal)
with automatic load and slip compensation to ensure
a constant speed at varying loads. Compensations
are active, but may be disabled in parameter 134
Load
compensation
and parameter 136
Slip compensation
as
required.
If
Speed control, closed loop
[1] is selected, better
speed accuracy is obtained. A feedback signal must
be added, and the PID regulator must be set in pa-
rameter group 400
Special functions
.
If
Process control, closed loop
[3] is selected, the inter-
nal process regulator is activated to enable precise
control of a process in relation to a given process sig-
nal. The process signal can be set to the relevant
process unit or as a percentage. A feedback signal
must be added from the process and the process reg-
ulator must be set in parameter group 400
Special
functions
. Process closed loop is not active if a Devi-
ceNet card is mounted and Instance 20/70 or 21/71 is
chosen in parameter 904
Instance types
.
101
Torque characteristic
Value:
Constant torque
(Constant
torque)
[1]
Variable torque low
(torque:
low)
[2]
Variable torque medium
(torque:
med)
[3]
Variable torque high
(torque:
high)
[4]
Variable torque low with CT start
(VT
LOW
CT
START)
[5]
Variable torque medium with CT start
(VT
MED
CT
START)
[6]
Variable torque high with CT start
(VT
HIGH
CT
START)
[7]
Special motor mode
(Special
motor
mode)
[8]
CT = Constant torque
Function:
This parameter enables a choice of principle for adap-
tation of the U/f ratio of the frequency converter to
the torque characteristic of the load. See par. 135
U/f
ratio
.
Description of choice:
If
Constant torque
[1] is selected, a load-dependent U/
f characteristic is obtained, in which output voltage
and output frequency are increased at increasing
loads in order to maintain constant magnetization of
the motor.
Select
Variable torque low
[2],
Variable torque medium
[3] or
Variable torque high
[4], if the load is square
(centrifugal pumps, fans).
Variable torque - low with CT start
[5],
- medium with CT
start
[6] or
high with CT start
[7], are selected if you
need a greater breakaway torque than can be ach-
ieved with the three first characteristics.
NOTE:
Load and slip compensation are not active if variable
torque or special motor mode have been selected.
Select
Special motor mode
[8], if a special U/f setting is
needed that is to be adapted to the present motor.
The break points are set in parameters 423-428
Volt-
age/frequency
.
24
TR1
2800
Series
VFD
Load and Motor
Programming
Содержание VarioTrane TR1 2800 Series
Страница 2: ...T TR R1 1 2 28 80 00 0 S Se er ri ie es s V VF FD D 1 1...
Страница 3: ...2 2 T TR R1 1 2 28 80 00 0 S Se er ri ie es s V VF FD D...
Страница 4: ...TR1 2800 Series VFD 3...
Страница 7: ...6 TR1 2800 Series VFD...
Страница 87: ...Illustration 5 7 192H4719 Illustration 5 8 192H4720 86 TR1 2800 Series VFD...
Страница 95: ...Branch Circuit Protection Short circuit protection 94 TR1 2800 Series VFD...
Страница 107: ...All about TR1 2800 Series VFD 106 TR1 2800 Series VFD...