According to international stand-
ards
Type
2805
2807
2811
2815
2822
2830
Output
current
IINV. [A]
1.7
2.1
3.0
3.7
5.2
7.0
(3 x 380-480V)
IMAX (60s)
[A]
2.7
3.3
4.8
5.9
8.3
11.2
Output power (400 V)
SINV. [KVA]
1.1
1.7
2.0
2.6
3.6
4.8
Typical shaft output
PM,N [kW]
0.55
0.75
1.1
1.5
2.2
3.0
Typical shaft output
PM,N [HP]
0.75
1.0
1.5
2.0
3.0
4.0
Max. cable cross sec-
tion, motor
[mm2 /AWG] 1)
4/10
4/10
4/10
4/10
4/10
4/10
Input
current
IL,N [A]
1.6
1.9
2.6
3.2
4.7
6.1
(3 x 380-480 V)
IL,MAX(60s)[A]
2.6
3.0
4.2
5.1
7.5
9.8
Max. cable cross sec-
tion, power
[mm2 /AWG] 1)
4/10
4/10
4/10
4/10
4/10
4/10
Max. pre-fuses
IEC/UL2) [A]
20/20
20/20
20/20
20/20
20/20
20/20
Efficiency3)
[%]
96
96
96
96
96
96
Power
loss
at
100%
load
[W]
28
38
55
75
110
150
Weight
[kg]
2.1
2.1
2.1
2.1
3.7
3.7
Enclosure4
type IP
20
IP
20
IP
20
IP
20
IP
20
IP
20
According to international stand-
ards
Type
2840
2855
2875
2880
2881
2882
Output
current
IINV. [A]
9.1
12
16
24
32.0
37.5
(3 x 380-480V)
IMAX (60s) [A]
14.5
19.2
25.6
38.4
51.2
60.0
Output power (400 V)
SINV. [KVA]
6.3
8.3
11.1
16.6
22.2
26.0
Typical shaft output
PM,N [kW]
4.0
5.5
7.5
11.0
15.0
18.5
Typical shaft output
PM,N [HP]
5.0
7.5
10.0
15.0
20.0
25.0
Max. cable cross sec-
tion, motor
[mm2 /AWG] 1)
4/10
4/10
4/10
16/6
16/6
16/6
Input
current
IL,N [A]
8.1
10.6
14.9
24.0
32.0
37.5
(3 x 380-480 V)
IL,MAX(60s)[A]
13.0
17.0
23.8
38.4
51.2
60
Max. cable cross sec-
tion, power
[mm2 /AWG] 1)
4/10
4/10
4/10
16/6
16/6
16/6
Max. pre-fuses
IEC/UL2) [A]
20/20
25/25
25/25
50/50
50/50
50/50
Efficiency3)
[%]
96
96
96
97
97
97
Power
loss
at
100%
load
[W]
200
275
372
412
562
693
Weight
[kg]
3.7
6.0
6.0
18.5
18.5
18.5
Enclosure4
type
IP20
IP20
IP20
IP20/
NEMA 1
IP20/
NEMA 1
IP20/
NEMA 1
1. American Wire Gauge. Max. cable cross section is the largest cable cross section that can be attached to the
terminals. Always observe national and local regulations.
2. Type gG pre-fuses must be used for installation according to IEC rules. If you want to maintain UL/cUL you
must use pre-fuses of the type Bussmann KTN-R 200 V, KTS-R 500 V or Ferraz Shawmut, type ATMR (max. 30A).
The fuses must be placed for protection in a circuit that is capable of supplying a maximum of 10 0,000 amps
RMS (symmetrical), 500 V maximum.
3. Measured using a 25 m screened/armoured motor cable with a rated load and rated frequency.
4. IP20 is standard for TR1 2805-2875, whereas NEMA 1 is an option.
122
TR1
2800
Series
VFD
Technical Data, Mains Supply 3 x 380 - 480 V
All about TR1 2800 Series VFD
Содержание VarioTrane TR1 2800 Series
Страница 2: ...T TR R1 1 2 28 80 00 0 S Se er ri ie es s V VF FD D 1 1...
Страница 3: ...2 2 T TR R1 1 2 28 80 00 0 S Se er ri ie es s V VF FD D...
Страница 4: ...TR1 2800 Series VFD 3...
Страница 7: ...6 TR1 2800 Series VFD...
Страница 87: ...Illustration 5 7 192H4719 Illustration 5 8 192H4720 86 TR1 2800 Series VFD...
Страница 95: ...Branch Circuit Protection Short circuit protection 94 TR1 2800 Series VFD...
Страница 107: ...All about TR1 2800 Series VFD 106 TR1 2800 Series VFD...