To select
Profidrive
in the control word, parameter 512
Telegram Profile
must be set to
Profidrive
[0].
The control word is used to send commands from a
master (e.g. a PC) to a slave (frequency converter).
MasterSlave.
Bit
Bit
=
0
Bit
=1
00
OFF
1
ON
1
01
OFF
2
ON
2
02
OFF
3
ON
3
03
Coasting
stop
04
Quick
stop
05
Freeze outp. freq.
06
Ramp
stop
Start
07
Reset
08
Bus
jog
1
09
Bus
jog
2
10
Data not valid
Data valid
11
Slow
down
12
Catch-up
13
Select Setup (lsb)
14
Select Setup (msb)
15
Reversing
Bit 00-01-02, OFF1-2-3/ON1-2-3:
Bit 00-01-02 = '0' causes ramp stop, which uses the
ramp time in parameters 207/208 or 209/210.
If
Relay 123
is selected in parameter 323
Relay out-
put
, the output relay will be activated when the output
frequency is 0 Hz.
Bit 00-01-02 = '1' means that the frequency converter
can start the motor if the other starting conditions are
fulfilled.
Bit 03, Coasting stop:
See description under
Control word according to FC
protocol.
Bit 04, Quick stop:
See description under
Control word according to FC
protocol.
Bit 05, Freeze output frequency:
See description under
Control word according to FC
protocol.
Bit 06, Ramp stop/start:
See description under
Control word according to FC
protocol.
Bit 07, Reset:
See description under
Control word according to FC
protocol.
Bit 08, Jog 1:
Bit 08 = "1" means that the output frequency is deter-
mined by parameter 09
Bus jog 1
.
Bit 09, Jog 2:
Bit 09 = "1" means that the output frequency is deter-
mined by parameter 510
Bus jog 2
.
Bit 10, Data not valid/Data valid:
See description under
Control word according to FC
protocol.
Bit 11, Slow-down:
Used to reduce the speed reference by the value in
parameter 219
Catch-up/slow-down reference
.
Bit 11 = '0' does not cause any change to the refer-
ence.
Bit 11 = '1' means that the reference is reduced.
Bit 12, Catch-up:
Used to increase the speed reference by the value in
parameter 219
Catch-up/slow-down reference
.
Bit 12 = '0' does not cause any change to the refer-
ence.
Bit 12 = '1' means that the reference is increased.
If both
Slow down
and
Catch-up
are activated (Bits 11
and 12 = "1"), slow down has the highest priority, i.e.
that the speed reference is reduced.
Bit 13/14, Selection of Setup:
See description under
Control word according to FC
protocol.
Bit 15 Reversing:
See description under
Control word according to FC
protocol.
TR1
2800
Series
VFD
67
Control Word According to Fieldbus Profile
Programming
Содержание VarioTrane TR1 2800 Series
Страница 2: ...T TR R1 1 2 28 80 00 0 S Se er ri ie es s V VF FD D 1 1...
Страница 3: ...2 2 T TR R1 1 2 28 80 00 0 S Se er ri ie es s V VF FD D...
Страница 4: ...TR1 2800 Series VFD 3...
Страница 7: ...6 TR1 2800 Series VFD...
Страница 87: ...Illustration 5 7 192H4719 Illustration 5 8 192H4720 86 TR1 2800 Series VFD...
Страница 95: ...Branch Circuit Protection Short circuit protection 94 TR1 2800 Series VFD...
Страница 107: ...All about TR1 2800 Series VFD 106 TR1 2800 Series VFD...