427
U3 voltage
Value:
0.0 - 999.0 V
par. 103
Function:
See parameter 423
U1 voltage
.
Description of choice:
Set the output voltage (U3) that is to match the third
output frequency (F3), parameter 428
F3 frequency
.
428
F3 frequency
Value:
Par. 426
F2 frequency
- 1000 Hz
Par. 104
Motor
frequency
Function:
See parameter 423
U1 voltage
.
Description of choice:
Set the output frequency (F3) that is to match the third
output voltage (U3), parameter 427
U3 voltage
.
NOTE:
Parameters 437-444 are only used if in parameter 100
Configuration
a selection has been made of
Process
regulation, closed loop.
[3].
437
Process PID normal/inverse control
Value:
Normal
(normal)
[0]
Inverse
(inverse)
[1]
Function:
It is possible to choose whether the process regulator
is to increase/reduce the output frequency if there is
a deviation between the reference/setpoint and the
actual process mode.
Description of choice:
If the adjustable frequency drive is to reduce the out-
put frequency in case the feedback signal increases,
select
Normal
[0].If the adjustable frequency drive is
to increase the output frequency in case the feedback
signal increases, select
Inverse
[1].
438
Proces PID anti windup
Value:
Not
active
(DISABLE)
[0]
Active
(ENABLE)
[1]
Function:
It is possible to select whether the process regulator
is to continue regulating on a deviation even if it is
not possible to increase/reduce the output frequency.
Description of choice:
The factory setting is
Enable
[1], which means that the
integration link is initialised in relation to the actual
output frequency if either the current limit, the volt-
age limit or the max./min. frequency has been
reached. The process regulator will not engage again
until either the error is zero or its sign has changed.
Select
Disable
[0] if the integrator is to continue inte-
grating on the deviation, even if it is not possible to
remove the fault by such control.
NOTE:
If
Disable
[0] is selected, it will mean that when the
deviation changes its sign, the integrator will first
have to integrate down from the level obtained as a
result of the former error, before any change in out-
put frequency occurs.
439
Process PID start frequency
Value:
f MIN - f MAX (pa-
rameter 201/202)
Par. 201
Output frequency,
low limit, f MIN
Function:
When the start signal comes, the adjustable frequen-
cy drive will react in the form of
Open loop
and will not
change to
Closed loop
until the programmed start fre-
quency is reached. This makes it possible to set a
frequency that corresponds to the speed at which the
process normally runs, which will enable the required
process conditions to be reached sooner.
Description of choice:
Set the required start frequency.
NOTE:
If the adjustable frequency drive is running a the cur-
rent limit before the required start frequency is ob-
tained, the process regulator will not be activated. For
the regulator to be activated anyway, the start fre-
quency must be lower to the required output fre-
quency. This can be done during operation.
440
Proces PID proportioanl gain
Value:
0.0 - 10.00
0.01
Function:
The proportional gain indicates the number of times
the deviation between the setpoint and the feedback
signal is to be applied.
Description of choice:
Quick regulation is obtained by a high gain, but if the
gain is too high, the process may become unstable
due to overshoot.
TR1
2800
Series
VFD
51
Programming
Содержание VarioTrane TR1 2800 Series
Страница 2: ...T TR R1 1 2 28 80 00 0 S Se er ri ie es s V VF FD D 1 1...
Страница 3: ...2 2 T TR R1 1 2 28 80 00 0 S Se er ri ie es s V VF FD D...
Страница 4: ...TR1 2800 Series VFD 3...
Страница 7: ...6 TR1 2800 Series VFD...
Страница 87: ...Illustration 5 7 192H4719 Illustration 5 8 192H4720 86 TR1 2800 Series VFD...
Страница 95: ...Branch Circuit Protection Short circuit protection 94 TR1 2800 Series VFD...
Страница 107: ...All about TR1 2800 Series VFD 106 TR1 2800 Series VFD...