Selection of Setup
Value:
Digital input (DIGITAL INPUT)
[0]
Serial communication (SERIAL PORT)
[1]
Logic
and
(LOGIC
AND)
[2]
Logic
or
(LOGIC
OR)
[3]
Function:
See function description of parameter 502
Coasting
stop.
Description of choice:
The table below shows which Setup (parameter 004
Active Setup
) is selected for each of the following:
Digital input
[0],
Serial communication
[1],
Logic and
[2]
or
Logic or
[3].
Digital input
[0]
Setup msb
Setup lsb
Function
0
0
Setup
1
0
1
Setup
2
1
0
Setup
3
1
1
Setup
4
Serial communication
[1]
Setup msb
Setup lsb
Function
0
0
Setup
1
0
1
Setup
2
1
0
Setup
3
1
1
Setup
4
Logic and
[2]
Bus Set-
up
msb
Bus Set-
up
lsb
Dig. Set-
up
msb
Dig. Set-
up
lsb
Setup
no.
0
0
0
0
1
0
0
0
1
1
0
0
1
0
1
0
0
1
1
1
0
1
0
0
1
0
1
0
1
2
0
1
1
0
1
0
1
1
1
2
1
0
0
0
1
1
0
0
1
1
1
0
1
0
3
1
0
1
1
3
1
1
0
0
1
1
1
0
1
2
1
1
1
0
3
1
1
1
1
4
Logic or
[3]
Bus Set-
up
msb
Bus Set-
up
lsb
Dig. Set-
up
msb
Dig. Set-
up
lsb
Setup
no.
0
0
0
0
1
0
0
0
1
2
0
0
1
0
3
0
0
1
1
4
0
1
0
0
2
0
1
0
1
2
0
1
1
0
4
0
1
1
1
4
1
0
0
0
3
1
0
0
1
4
1
0
1
0
3
1
0
1
1
4
1
1
0
0
4
1
1
0
1
4
1
1
1
0
4
1
1
1
1
4
74
TR1
2800
Series
VFD
Programming
Содержание VarioTrane TR1 2800 Series
Страница 2: ...T TR R1 1 2 28 80 00 0 S Se er ri ie es s V VF FD D 1 1...
Страница 3: ...2 2 T TR R1 1 2 28 80 00 0 S Se er ri ie es s V VF FD D...
Страница 4: ...TR1 2800 Series VFD 3...
Страница 7: ...6 TR1 2800 Series VFD...
Страница 87: ...Illustration 5 7 192H4719 Illustration 5 8 192H4720 86 TR1 2800 Series VFD...
Страница 95: ...Branch Circuit Protection Short circuit protection 94 TR1 2800 Series VFD...
Страница 107: ...All about TR1 2800 Series VFD 106 TR1 2800 Series VFD...