Some frequency converters have parameters to
which a text may be written. To be able to write a text
via the PWE block the parameter command (AK) must
be set to 'F' Hex.
For a write command the text must have the follow-
ing format:
Data types supported by frequency transformer:
Data types
Description
3
Integer 16
4
Integer 32
5
Unsigned 8
6
Unsigned 16
7
Unsigned 32
9
Text string
Unsigned means that there is no operational sign in
the telegram.
Example - Write a parameter value:
Parameter 202
Output frequency high limit, f MAX
to be
changed to 100 Hz. The value must be recalled after
a mains failure, so it is written in EEPROM.
PKE = E0CA Hex - Write for parameter 202
Output
frequency high limit, f MAX
IND = 0000 Hex
PWEHIGH = 0000 Hex
PWELOW = 03E8 Hex - Data value 1000, corre-
sponding to 100 Hz, see conversion.
The response from the slave to the master will be:
Example - Selection of a data value:
You wish to select kg/hour [20] in parameter 416
Process units
. The value must be recalled after a mains
failure, so it is written in EEPROM.
PKE = E19F Hex - Write for parameter 416
Process
units
IND = 0000 Hex
PWEHIGH = 0000 Hex
PWELOW = 0014 Hex - Select data option kg/hour
[20]
The response from the slave to the master will be:
60
TR1
2800
Series
VFD
Programming
Содержание VarioTrane TR1 2800 Series
Страница 2: ...T TR R1 1 2 28 80 00 0 S Se er ri ie es s V VF FD D 1 1...
Страница 3: ...2 2 T TR R1 1 2 28 80 00 0 S Se er ri ie es s V VF FD D...
Страница 4: ...TR1 2800 Series VFD 3...
Страница 7: ...6 TR1 2800 Series VFD...
Страница 87: ...Illustration 5 7 192H4719 Illustration 5 8 192H4720 86 TR1 2800 Series VFD...
Страница 95: ...Branch Circuit Protection Short circuit protection 94 TR1 2800 Series VFD...
Страница 107: ...All about TR1 2800 Series VFD 106 TR1 2800 Series VFD...