If the active motor current is below 10%, the motor
voltage will be decreased by the speed mentioned
above until the voltage reaches the setting for Par.
117. If the active motor current comes over 20% the
voltage will be increased by the above mentioned
speed. If the active motor current reaches 40% the
motor voltage will be increased immediately to nor-
mal motor voltage.
The reduction in motor voltage depends on the pa-
rameter 117 setting.
Description of choice:
Set the grade of Motor current [Imact] influence on
the U/F ratio between 0% (OFF) and 100%. 100% cor-
responds to 50% reduction of U/F ratio. Default value
is OFF.
119
High start torque
Value:
0.0 - 0.5 sec.
0.0 sec.
Function:
To ensure a high start torque approx. 1.8 x I INV. can
be permitted for max. 0.5 sec. The current is, howev-
er, limited by the frequency converter's (inverter's)
safety limit. 0 sec. corresponds to no high start tor-
que.
Description of choice:
Set the necessary time for which a high start torque
is required.
120
Start delay
Value:
0.0 - 10.0 sec.
0.0 sec.
Function:
This parameter enables a delay of the start-up time
after the conditions for start have been fulfilled. When
the time has passed, the output frequency will start
by ramping up to the reference.
Description of choice:
Set the necessary time before commencing to accel-
erate.
121
Start function
Value:
DC hold during start delay time
(DC
HOLD/DELAY
TIME)
[0]
DC brake during start delay time
(DC BRAKE/DELAY TIME)
[1]
Coasting during start delay time
(COAST/DELAY
TIME)
[2]
Start frequency/voltage clockwise
(CLOCKWISE OPERATION)
[3]
Start frequency/voltage in reference direction
(VERTICAL
OPERATION)
[4]
Function:
This is where to choose the required mode during the
start delay time (parameter 120
Start delay time
).
Description of choice:
Select
DC hold during start delay time
[0] to energize
the motor with a DC hold voltage during the start de-
lay time. Set voltage in parameter 137
DC hold volt-
age
.
Choose
DC brake during start delay time
[1] to energize
the motor with a DC brake voltage during the start
delay time. Set voltage in parameter 132
DC brake
voltage
.
Choose
Coasting during start delay time
[2] and the
motor will not be controlled by the adjustable fre-
quency drive during the start delay time (inverter
turned off).
Choose
Start frequency/voltage clockwise
[3] to obtain
the function described in parameter 130
Start fre-
quency
and 131
Voltage at start
during start delay
time. Regardless of the value assumed by the refer-
ence signal, the output frequency equals the setting
in parameter 130
Start frequency
and the output volt-
age will correspond to the setting in parameter 131
Voltage at start
.
This functionality is typically used in hoist applica-
tions. It is used in particular in applications in which
a cone anchor motor is applied, where the direction
of rotation is to start clockwise followed by the refer-
ence direction.
Select
Start frequency/voltage in reference direction
[4]
to obtain the function described in parameter 130
Start frequency
and 131
Voltage at start
during the start
delay time.
The direction of rotation of the motor will always fol-
low in the reference direction. If the reference signal
equals zero, the output frequency will equal 0 Hz,
while the output voltage will correspond to the set-
ting in parameter 131
Voltage at start
. If the reference
signal is different from zero, the output frequency will
equal parameter 130
Start frequency
and the output
TR1
2800
Series
VFD
27
Programming
Содержание VarioTrane TR1 2800 Series
Страница 2: ...T TR R1 1 2 28 80 00 0 S Se er ri ie es s V VF FD D 1 1...
Страница 3: ...2 2 T TR R1 1 2 28 80 00 0 S Se er ri ie es s V VF FD D...
Страница 4: ...TR1 2800 Series VFD 3...
Страница 7: ...6 TR1 2800 Series VFD...
Страница 87: ...Illustration 5 7 192H4719 Illustration 5 8 192H4720 86 TR1 2800 Series VFD...
Страница 95: ...Branch Circuit Protection Short circuit protection 94 TR1 2800 Series VFD...
Страница 107: ...All about TR1 2800 Series VFD 106 TR1 2800 Series VFD...