Electrical Installation
Comply with the following at installation:
•
Safety earthing: The drive has a high leakage current and must be earthed properly for safety. Follow
all local safety regulations.
•
High frequency earthing: Keep earthing connections as short as possible.
Connect all earthing systems to ensure the lowest possible conductor impedance. The lowest possible conductor
impedance is achieved by keeping the conductor as short as possible and by grounding with the greatest pos-
sible surface area. If multiple drives are installed in a cabinet, the cabinet backplate, which must be made of
metal, should be used as a joint earth reference plate. The drives must be fitted to the backplate at the lowest
possible impedance.
To achieve low impedance, connect the drive to the backplate with the drive fastening bolts. Remove all paint
from the contact points.
RCD relays, multiple protective earthing or earthing can be used as extra protection, provided that local safety
regulations are complied with. In the case of an earth fault, a DC content may develop in the faulty current. Never
use an RCD (ELCB relay), type A, as it is not suitable for DC faulty currents. If RCD relays are used, local regu-
lations must be complied with.If RCD relays are used, they must be:
-
Suitable for protecting equipment with a DC content in the faulty current (3-phase bridge rectifier).
-
Suitable for a pulse-shaped, brief discharge on power-up.
-
Suitable for a high leakage current.
N must be connected before L1 for single phase 200 V reduced leakage current units (type code R4).
TR1
2800
Series
VFD
89
Safety Requirements of Electrical Installation
High Voltage Warning
WARNING
The voltage of the frequency converter is dangerous whenever the equipment is connected to mains. Incorrect instal-
lation of the motor or frequency converter may cause damage to the equipment, serious injury or dea th. Comply with
the instructions in this manual, as well as national and local rules and safety regulations. Touching the electrical parts
may be fatal - even after the equipment has been disconnected from mains: Wait at least 4 minutes for currents
dissipate.
NOTICE
It is the responsibility of the user or installer to ensure correct earthing and protection in accordance with national and
local standards.
Earthing
Extra Protection
Содержание VarioTrane TR1 2800 Series
Страница 2: ...T TR R1 1 2 28 80 00 0 S Se er ri ie es s V VF FD D 1 1...
Страница 3: ...2 2 T TR R1 1 2 28 80 00 0 S Se er ri ie es s V VF FD D...
Страница 4: ...TR1 2800 Series VFD 3...
Страница 7: ...6 TR1 2800 Series VFD...
Страница 87: ...Illustration 5 7 192H4719 Illustration 5 8 192H4720 86 TR1 2800 Series VFD...
Страница 95: ...Branch Circuit Protection Short circuit protection 94 TR1 2800 Series VFD...
Страница 107: ...All about TR1 2800 Series VFD 106 TR1 2800 Series VFD...