4-17
Code
Name
Data setting range
C
ha
nge
w
hen
runnin
g
D
a
ta
c
op
y
ing
Default
setting
Drive Control
Refer to
Page
V/f
Vector
Control
w/
PG
Torque
control
w/o
PG
A18 Motor 2
(Auto-tuning)
0: Disable
1: Tune while the motor stops. (%R1, %X and
rated slip frequency)
2: Tune while the motor is rotating under V/f
control (%R1, %X, rated slip frequency, no-load
current, magnetic saturation factors 1 to 5, and
magnetic saturation extension factors "a" to "c")
3: Tune while the motor is rotating under vector
control (%R1, %X, rated slip frequency, no-load
current, magnetic saturation factors 1 to 5, and
magnetic saturation extension factors "a" to "c."
Available when the vector control is enabled.
N
N
0
Y
Y
Y
Y
*11
A19
(Online tuning)
0: Disable 1: Enable
Y
Y
0
Y
N
N
N
A20
(No-load current)
0.00 to 2000 A
N
Y1
Y2
*7
Y
Y
Y
Y
A21
(%R1)
0.00% to 50.00%
Y
Y1
Y2
*7
Y
Y
Y
Y
A22
(%X)
0.00% to 50.00%
Y
Y1
Y2
*7
Y
Y
Y
Y
A23 (Slip compensation gain for driving)
0.0% to 200.0%
Y*
Y
100.0
Y
Y
Y
N
A24 (Slip compensation response time)
0.01 to 10.00s
Y
Y1
Y2
0.12
Y
N
N
N
A25 (Slip compensation gain for braking)
0.0% to 200.0%
Y*
Y
100.0
Y
Y
Y
N
A26
(Rated slip frequency)
0.00 to 15.00 Hz
N
Y1
Y2
*7
Y
Y
Y
N
A27
(Iron loss factor 1)
0.00% to 20.00%
Y
Y1
Y2
*7
Y
Y
Y
Y
A28
(Iron loss factor 2)
0.00% to 20.00%
Y
Y1
Y2
0.00
Y
Y
Y
Y
A29
(Iron loss factor 3)
0.00% to 20.00%
Y
Y1
Y2
0.00
Y
Y
Y
Y
A30 (Magnetic saturation factor 1)
0.0% to 300.0%
Y
Y1
Y2
*7
Y
Y
Y
Y
A31 (Magnetic saturation factor 2)
0.0% to 300.0%
Y
Y1
Y2
*7
Y
Y
Y
Y
A32 (Magnetic saturation factor 3)
0.0% to 300.0%
Y
Y1
Y2
*7
Y
Y
Y
Y
A33 (Magnetic saturation factor 4)
0.0% to 300.0%
Y
Y1
Y2
*7
Y
Y
Y
Y
A34 (Magnetic saturation factor 5)
0.0% to 300.0%
Y
Y1
Y2
*7
Y
Y
Y
Y
A35 (Magnetic saturation extension
factor "a")
0.0% to 300.0%
Y
Y1
Y2
*7
Y
Y
Y
Y
A36 (Magnetic saturation extension
factor "b")
0.0% to 300.0%
Y
Y1
Y2
*7
Y
Y
Y
Y
A37 (Magnetic saturation extension
factor "c")
0.0% to 300.0%
Y
Y1
Y2
*7
Y
Y
Y
Y
A39 Motor 2 Selection
0: Motor characteristics 0 ( Consult Factory)
1: Motor characteristics 1 (HP rating motors)
2: Motor characteristics 2 (Consult Factory)
3: Motor characteristics 3 (Consult Factory)
4: Consult Factory
N
Y1
Y2
1
Y
Y
Y
Y
A40 Slip Compensation 2
(Operating conditions)
0: Enable during ACC/DEC and at base frequency
or above
1: Disable during ACC/DEC and enable at base
frequency or above
2: Enable during ACC/DEC and disable at base
frequency or above
3: Disable during ACC/DEC and at base frequency
or above
N
Y
0
Y
N
N
N
A41 Output Current Fluctuation Damping
Gain for Motor 2
0.00 to 1.00
Y
Y
0.20
Y
N
N
N
A42 Motor/Parameter Switching 2
(Mode selection)
0: Motor (Switch to the 2nd motor)
1: Parameter (Switch to particular A codes)
N
Y
0
Y
Y
Y
Y
4-73
A43 Speed Control 2
(Speed command filter)
0.000 to 5.000 s
Y
Y
0.020
N
Y
Y
N
*11
A44
(Speed detection filter)
0.000 to 0.100 s
Y*
Y
0.005
N
Y
Y
N
A45
P (Gain)
0.1 to 200.0 times
Y*
Y
10.0
N
Y
Y
N
A46
I (Integral time)
0.001 to 9.999 s
999: Disable integral action
Y*
Y
0.100
N
Y
Y
N
A48
(Output filter)
0.000 to 0.100 s
Y
Y
0.002
N
Y
Y
N
A49 (Notch filter resonance frequency)
1 to 200 Hz
Y
Y
200
N
N
Y
N
A50 (Notch filter attenuation level)
0 to 20 dB
Y
Y
0
N
N
Y
N
A51 Cumulative Motor Run Time 2
0 to 99990 hours
(The cumulative run time can be modified or
reset.)
N
N
-
Y
Y
Y
Y
A52 Startup Counter for Motor 2
Indication of cumulative startup count
0 to 65535 times
Y
N
-
Y
Y
Y
Y
Содержание EQ7 Series
Страница 1: ......
Страница 29: ...2 6 Unit inch mm Refer to Section 2 3 3 9 ...
Страница 94: ...4 25 Table B Motor Parameters Continued Three phase 460 V series EQ7 4_ _ _ C ...