10-19
[ 17 ]
PG wire break
Problem The pulse generator (PG) wire has been broken somewhere in the circuit.
Possible Causes
What to Check and Suggested Measures
(1) The wire between the pulse
generator (PG) and the
option card has been
broken.
Check whether the pulse generator (PG) is correctly connected to the option card
or any wire is broken.
Check whether the PG is connected correctly. Or, tighten up the related
terminal screws.
Check whether any joint or connecting part bites the wire sheath.
Replace the wire.
(2) PG related circuit affected
by strong electrical noise.
Check if appropriate noise control measures have been implemented (e.g.,
correct grounding and routing of signal wires, communication cables, and main
circuit wires).
Implement noise control measures.
Separate the signal wires from the main power wires as far as possible.
[ 18 ]
Memory error
Problem Error occurred in writing the data to the memory in the inverter.
Possible Causes
What to Check and Suggested Measures
(1) When writing data
(especially initializing or
copying data), the inverter
was shut down so that the
voltage to the control PCB
has dropped.
Initialize the function code data with H03 (= 1). After initialization, check if
pressing the
key releases the alarm.
Revert the initialized function code data to their previous settings, then restart
the operation.
(2) Inverter affected by strong
electrical noise when writing
data (especially initializing
or copying data).
Check if appropriate noise control measures have been implemented (e.g.,
correct grounding and routing of control and main circuit wires). Also, perform the
same check as described in (1) above.
Implement noise control measures. Revert the initialized function code data
to their previous settings, then restart the operation.
(3) The control PCB failed.
Initialize the function code data by setting H03 to "1," then reset the alarm by
pressing the
key and check that the alarm goes on.
The control PCB (on which the CPU is mounted) is defective. Contact your
TECO-Westinghouse Motor Company representative.
[ 19 ]
Keypad communications error
Problem A communications error occurred between the multi-function keypad and the inverter.
Possible Causes
What to Check and Suggested Measures
(1) Broken communications
cable or poor contact.
Check continuity of the cable, contacts and connections.
Re-insert the connector firmly.
Replace the cable.
(2) Connecting many control
wires hinders the front cover
from being mounted, lifting
the keypad.
Check the mounting condition of the front cover.
Use wires of the recommended size AWG 19 or 18 (0.65 to 0.82 mm
2
) for
wiring.
Change the wiring layout inside the unit so that the front cover can be
mounted firmly.
(3) Inverter affected by strong
electrical noise.
Check if appropriate noise control measures have been implemented (e.g.,
correct grounding and routing of communication cables and main circuit wires).
Implement noise control measures.
For details, refer to the EQ7 User's Manual, "Appendix A."
(4) A keypad failure occurred.
Replace the keypad with another one and check whether a keypad
communications error (
) occurs.
Replace the keypad.