4-5
Code
Name
Data setting range
C
ha
nge
w
hen
run
ning
D
a
ta
c
op
y
in
g
Default
setting
Drive control
Refer to
Page
V/f
Vector
Control
w/
PG
Torque
control
w/o
PG
F37 Load Selection/
Auto Torque Boost/
Auto Energy Saving Operation 1
0: Variable torque load
1: Constant torque load
2: Auto torque boost
3: Auto energy saving
(Variable torque load during ACC/DEC)
4: Auto energy saving
(Constant torque load during
ACC/DEC)
5: Auto energy saving
(Auto torque boost during ACC/DEC)
N
Y
1
Y
N
Y
N
4-56
F38 Stop Frequency(Detection mode)
0: Detected speed
1: Reference speed
N
Y
0
N
N
Y
N
4-58
F39
(Holding Time)
0.00 to 10.00 s
Y
Y
0.00
Y
Y
Y
N
F40 Torque Limiter
1-1
-300% to 300%; 999 (Disable)
Y
Y
999
Y
Y
Y
Y
F41
1-2
-300% to 300%; 999 (Disable)
Y
Y
999
Y
Y
Y
Y
F42 Drive Control Selection 1
0: V/f control with slip compensation
inactive
1: Dynamic torque control
5: Vector control without speed sensor
6: Vector control with speed sensor
N
Y
0
Y
Y
Y
Y
4-65
F43 Current Limiter (Mode selection)
0: Disable (No current limiter works.)
1: Enable at constant speed (Disable during
ACC/DEC)
2: Enable during ACC/constant speed
operation
Y
Y
2
Y
N
N
N
4-67
F44
(Level) 20% to 200% (The data is interpreted as
the rated output current of the inverter for
100%.)
Y
Y
*5
Y
N
N
N
F50 Electronic Thermal Overload Protection for
Braking Resistor
(Discharging capability)
0 (Braking resistor built-in type), 1 to 9000
kWs,
OFF (Disable)
Y
Y1 Y2
*6
Y
Y
Y
Y
4-68
F51
(Allowable average loss) 0.001 to 99.99 kW
Y
Y1 Y2 0.001
Y
Y
Y
Y
F52
(Resistance)
0.01 to 999Ω
Y
Y1 Y2 0.01
Y
Y
Y
Y
F80 Switching between LD, MD and HD drive
modes
1: LD (Variable Torque mode)
2: MD (Constant Torque mode)
0: HD (CT-Vector mode)
N
Y
1
Y
Y
Y
Y
4-69
The shaded function codes are applicable to the quick setup.
*1 6.00 s for inverters of 40 HP or below; 20.00 s for those of 50 HP or above
*2 The motor rated current is automatically set. See Table B (P03/A17).
*3 5.0 min for inverters of 40 HP or below; 10.0 min for those of 50 HP or above
*4 0% to 100% for inverters of 7.5 HP or below
*5 160% for inverters of 7.5 HP or below; 130% for those of 10 HP or above
*6 0 for inverters of 15 HP or below; OFF for those of 20 HP or above
The shaded function codes are applicable to the quick setup.
Y: Applicable / N: Not Applicable.