4-38
Under vector control without speed sensor
Under vector control with speed sensor
Acceleration/deceleration time
Acceleration/
deceleration time
Function code
Switching factor of acceleration/deceleration time
(
Refer to the descriptions of E01 to E07.)
ACC
time
DEC
time
Acceleration/
deceleration time 1
F07
F08
RT1
RT2
The combinations of ON/OFF states of the
two terminal commands
RT2
and
RT1
offer
four choices of acceleration/deceleration
time 1 to 4.
(Data = 4, 5)
If no terminal command is assigned, only the
acceleration/deceleration time 1 (F07/F08) is
effective.
OFF
OFF
Acceleration/
deceleration time 2
E10
E11
OFF
ON
Acceleration/
deceleration time 3
E12
E13
ON
OFF
Acceleration/
deceleration time 4
E14
E15
ON
ON
At jogging operation
H54
H55
When the terminal command
JOG
is ON, jogging operation
is possible. (Data = 10)
(
Refer to the description of C20.)
At forced stop
-
H56
When the terminal command
STOP
is OFF, the motor
decelerates to a stop in accordance with the deceleration
time for forced stop (H56). After the motor stops, the inverter
enters the alarm state with the alarm
er6
displayed. (Data =
30)