4-15
Code
Name
Data setting range
C
ha
nge
w
hen
runnin
g
D
a
ta
c
op
y
in
g
Default
setting
Drive Control
Refer to
Page
V/f
Vector
Control
w/
PG
Torque
control
w/o
PG
H73 Torque Limiter
(Operating conditions)
0: Enable during ACC/DEC and running at
constant speed
1: Disable during ACC/DEC and enable during
running at constant speed
2: Enable during ACC/DEC and disable during
running at constant speed
N
Y
0
Y
Y
Y
Y
*11
H74
(Control target)
0: Motor-generating torque limit
1: Torque current limit
2: Output power limit
N
Y
1
N
Y
Y
Y
H75
(Target quadrants)
0: Drive/brake
1: Same for all four quadrants
2: Upper/lower limits
N
Y
0
N
Y
Y
Y
H76
(Frequency increment limit
for braking)
0.0 to 500.0 Hz
Y
Y
5.0
Y
N
N
N
H77 Service Life of DC Link Bus
Capacitor
(Remaining time)
0 to 87600 hours
Y
N
-
Y
Y
Y
Y
H78 Maintenance Interval (M1)
0: Disable; 1 to 99990 hours
Y
N
87600
Y
Y
Y
Y
H79 Preset Startup Count for
Maintenance (M1)
0: Disable; 1 to 65535 times
Y
N
0
Y
Y
Y
Y
H80 Output Current Fluctuation
Damping Gain for Motor 1
0.00 to 1.00
Y
Y
0.20
Y
N
N
Y
H81 Light Alarm Selection 1
0000 to FFFF (hex.)
Y
Y
0
Y
Y
Y
Y
H82 Light Alarm Selection 2
0000 to FFFF (hex.)
Y
Y
0
Y
Y
Y
Y
H84 Pre-excitation
(Initial level)
100% to 400%
Y
Y
100
N
Y
Y
Y
H85
(Time)
0.00: Disable; 0.01 to 30.00 s
Y
Y
0.00
N
Y
Y
Y
H86 Reserved *9
―
-
-
-
-
-
-
-
H87 Reserved *9
―
-
-
-
-
-
-
-
H88 Reserved *9
―
-
-
-
-
-
-
-
H89 Reserved *9
―
-
-
-
-
-
-
-
H90 Reserved *9
―
-
-
-
-
-
-
-
H91 PID Feedback Wire Break
Detection
0.0: Disable alarm detection
0.1 to 60.0 s
Y
Y
0.0
Y
Y
Y
N
H92 Continuity of Running
(P)
0.000 to 10.000 times; 999
Y
Y1Y2
999
Y
N
N
N
H93
(I)
0.010 to 10.000 s; 999
Y
Y1Y2
999
Y
N
N
N
H94 Cumulative Motor Run Time 1
0 to 99990 hours
(The cumulative run time can be modified or reset.)
N
N
-
Y
Y
Y
Y
H95 DC Braking
(Braking response mode)
0: Slow
1: Quick
Y
Y
1
Y
N
N
N
H96 STOP Key Priority/
Start Check Function
Data STOP key priority Start check function
0:
Disable
Disable
1:
Enable
Disable
2:
Disable
Enable
3:
Enable
Enable
Y
Y
3
Y
Y
Y
Y
H97 Clear Alarm Data
0: Disable
1: Enable (Setting "1" clears alarm data and then
returns to "0.")
Y
N
0
Y
Y
Y
Y
H98 Protection/Maintenance Function
(Mode selection)
0 to 255: Display data in decimal format
Bit 0: Lower the carrier frequency automatically
(0: Disabled; 1: Enabled)
Bit 1: Detect input phase loss
(0: Disabled; 1: Enabled)
Bit 2: Detect output phase loss
(0: Disabled; 1: Enabled)
Bit 3: Select life judgment threshold of DC link bus
capacitor
(0: Factory default level; 1: User setup level)
Bit 4: Judge the life of DC link bus capacitor
(0: Disabled; 1: Enabled)
Bit 5: Detect DC fan lock (0: Enabled; 1: Disabled)
Bit 6: Detect braking transistor error
(for 40 HP or below)
(0: Disabled; 1: Enabled)
Bit 7: Switch IP20/IP40 enclosure
(0: IP20; 1: IP40)
Y
Y
83
Y
Y
Y
Y
*9 Factory use. Do not access these function codes.
*11 Refer to the User Manual for detailed information on these parameters.
Y: Applicable / N: Not Applicable.