4-77
Example of Operation Time Scheme
Alternatively, set the integrated sequence by which some of the actions above are automatically
performed by the inverter itself. For details, refer to the description of
ISW50
and
ISW60
.
UP Increase output frequency) and DOWN (Decrease output frequency) commands --
UP
and
DOWN
(Function code data = 17 and 18)
•
Frequency setting
Turning the terminal command
UP
or
DOWN
ON causes the output frequency to increase or decrease,
respectively, within the range from 0 Hz to the maximum frequency.
Refer to F01 (data = 7).
•
PID command
Turning the terminal command
UP
or
DOWN
ON causes the PID command value to increase or decrease,
respectively, within the range from 0 to 100%.
Refer to J02 (data = 3).
Enable data change with keypad PID control --
WE-KP
(Function code data = 19)
Turning the terminal command
WE-KP
OFF protects function code data from accidentally getting changed by
pressing the keys on the keypad. Only when this terminal command is ON, you can change function code data
from the keypad.
Refer to F00.