4-14
Code
Name
Data setting range
C
ha
nge
w
hen
runnin
g
D
a
ta
c
op
y
in
g
Default
setting
Drive control
Refer to
Page
V/f
Vector
Control
w/
PG
Torque
control
w/o
PG
H49 Starting Mode
(Auto search delay time 1)
0.0 to 10.0 s
Y
Y
0.0
Y
Y
Y
Y
*11
H50 Non-linear V/f Pattern 1
(Frequency)
0.0: Cancel, 0.1 to 500.0 Hz
N
Y
0.0
Y
N
N
N
H51
(Voltage) 0 to 240:
Output an AVR-controlled voltage
(for 230 V series)
0 to 500:
Output an AVR-controlled voltage
(for 460 V series)
N
Y2
0
Y
N
N
N
H52 Non-linear V/f Pattern 2
(Frequency)
0.0: Cancel, 0.1 to 500.0 Hz
N
Y
0.0
Y
N
N
N
H53
(Voltage) 0 to 240:
Output an AVR-controlled voltage
(for 230 V series)
0 to 500:
Output an AVR-controlled voltage
(for 460 V series)
N
Y2
0
Y
N
N
N
H54 Acceleration Time
(Jogging) 0.00 to 6000 s
Y
Y
*1
Y
Y
Y
N
H55 Deceleration Time
(Jogging) 0.00 to 6000 s
Y
Y
*1
Y
Y
Y
N
H56 Deceleration Time for Forced
Stop
0.00 to 6000 s
Y
Y
*1
Y
Y
Y
N
H57 1st S-curve acceleration range
(Leading edge)
0% to 100%
Y
Y
10
Y
Y
Y
N
H58 2nd S-curve acceleration range
(Trailing edge)
0% to 100%
Y
Y
10
Y
Y
Y
N
H59 1st S-curve deceleration range
(Leading edge)
0% to 100%
Y
Y
10
Y
Y
Y
N
H60 2nd S-curve deceleration range
(Trailing edge)
0% to 100%
Y
Y
10
Y
Y
Y
N
H61 UP/DOWN Control
(Initial frequency setting)
0: 0.00 Hz
1: Last
UP
/
DOWN
command value on releasing the
run command
N
Y
1
Y
Y
Y
N
H63 Low Limiter
(Mode selection) 0: Limit by F16 (Frequency limiter: Low) and
continue to run
1: If the output frequency lowers below the one
limited by F16 (Frequency limiter: Low),
decelerate to stop the motor.
Y
Y
0
Y
Y
Y
N
H64
(Lower limiting frequency) 0.0: Depends on F16 (Frequency limiter, Low)
0.1 to 60.0 Hz
Y
Y
1.6
Y
N
N
N
H65 Non-linear V/f Pattern 3
(Frequency)
0.0: Cancel, 0.1 to 500.0 Hz
N
Y
0.0
Y
N
N
N
H66
(Voltage) 0 to 240:
Output an AVR-controlled voltage
(for 230 V series)
0 to 500:
Output an AVR-controlled voltage
(for 460 V series)
N
Y2
0
Y
N
N
N
H67 Auto Energy Saving Operation
(Mode selection)
0: Enable during running at constant speed
1: Enable in all modes
Y
Y
0
Y
N
Y
N
H68 Slip Compensation 1
(Operating conditions)
0: Enable during ACC/DEC and at base frequency
or above
1: Disable during ACC/DEC and enable at base
frequency or above
2: Enable during ACC/DEC and disable at base
frequency or above
3: Disable during ACC/DEC and at base frequency
or above
N
Y
0
Y
N
N
N
H69 Automatic Deceleration
(Mode selection)
0: Disable
2: Torque limit control with Force-to-stop if actual
deceleration time exceeds three times the
specified one
3: DC link bus voltage control with Force-to-stop if
actual deceleration time exceeds three times the
specified one
4: Torque limit control with Force-to-stop disabled
5: DC link bus voltage control with Force-to-stop
disabled
Y
Y
0
Y
Y
Y
N
H70 Overload Prevention Control
0.00:Follow the deceleration time selected
0.01 to 100.0 Hz/s
999: Cancel
Y
Y
999
Y
Y
Y
N
H71 Deceleration Characteristics
0: Disable
1: Enable
Y
Y
0
Y
N
N
N
H72 Main Power Down Detection
(Mode selection)
0: Disable
1: Enable
Y
Y
1
Y
Y
Y
Y
*
1 6.00 s for inverters of 40 HP or below; 20.00 s for those of 50 HP or above.
*11 Refer to the User Manual for detailed information on these parameters.
Y: Applicable / N: Not Applicable.