6-5
Set value
Frequency command
Run command (Run/Stop)
0
F01 / C30
F02
1
Enabled / RS485 (Port 1)
F02
2
F01 / C30
Enabled / RS485 (Port 1)
3
Enabled / RS485 (Port 1)
Enabled / RS485 (Port 1)
4
Enabled / RS485 (Port 2)
F02
5
Enabled / RS485 (Port 2)
Enabled / RS485 (Port 1)
6
F01 / C30
Enabled / RS485 (Port 2)
7
Enabled / RS485 (Port 1)
Enabled / RS485 (Port 2)
8
Enabled / RS485 (Port 2)
Enabled / RS485 (Port 2)
Frequency Reference Command Register
EQ7 Drive Frequency Reference Register: 1797 (Decimal) - Bit 0
– Bit 15: 0.00 ~ 120.00 Hz
Examples:
Frequency Reference Command: 10.00 Hz (EQ7 Drive Address: 01)
Command String (hexadecimal): 01 06 07 05 03 E8 98 01
To set the frequency reference to 10.00, a value of ‘1000’ (03E8h) has to be send to the EQ7 Drive
Frequency Reference Command: 30.00 Hz (EQ7 Drive Address: 01)
Command String (hexadecimal): 01 06 07 05 0B B8 9F FD
To set the frequency reference to 30.00, a value of ‘3000’ (0BB8h) has to be send to the EQ7 Drive
Frequency Reference Command: 60.00 Hz (EQ7 Drive Address: 01)
Command String (hexadecimal): 01 06 07 05 17 70 96 AB
To set the frequency reference to 60.00, a value of ‘6000’ (1770h) has to be send to the EQ7 Drive
Note:
The last 2 bytes of the command strings consist of a CRC16 checksum, please refer to the Refer to the EQ7
Communications Manual for additional information.