vi
• Before changing the switches or touching the control circuit terminal symbol plate,
turn OFF the
power and wait at least five minutes for inverters of 40 HP or below, or at least ten minutes
for inverters of 50 HP or above
. Make sure that the LED monitor and charging lamp are turned
OFF. Further, make sure, using a multimeter or a similar instrument, that the DC link bus voltage
between the terminals P(+) and N(-) has dropped to the safe level (+25 VDC or below).
Otherwise, an electric shock could occur.
• The inverter, motor and wiring generate electric noise. This may cause the malfunction of nearby
sensors and devices. To prevent malfunctioning, implement noise control measures.
Otherwise an accident could occur.
Operation
• Be sure to mount the front cover before turning the power ON. Do not remove the cover when the
inverter power is ON.
Otherwise, an electric shock could occur.
• Do not operate switches with wet hands.
Doing so could cause electric shock.
• If the auto-reset function has been selected, the inverter may automatically restart and drive the
motor depending on the cause of tripping. Design the machinery or equipment so that human safety
is ensured at the time of restarting.
Otherwise, an accident could occur.
• If the stall prevention function (current limiter), automatic deceleration (anti-regenerative control), or
overload prevention control has been selected, the inverter may operate with
acceleration/deceleration or frequency different from the commanded ones. Design the machine so
that safety is ensured even in such cases.
• If any of the protective functions have been activated, first remove the cause. Then, after checking
that the all run commands are set to OFF, release the alarm. If the alarm is released while any run
commands are set to ON, the inverter may supply the power to the motor, running the motor.
Otherwise, an accident could occur.
• If you enable the "Restart mode after momentary power failure" (Function code F14 = 3 to 5), then
the inverter automatically restarts running the motor when the power is recovered.
Design the machinery or equipment so that human safety is ensured after restarting.
• If the user configures the function codes wrongly without completely understanding this Instruction
Manual and the EQ7 DRIVE User's Manual, the motor may rotate with a torque or at a speed not
permitted for the machine.
An accident or injuries could occur.
• Even if the inverter has interrupted power to the motor, if the voltage is applied to the main circuit
input terminals L1/R, L2/S and L3/T, voltage may be output to inverter output terminals U, V, and W.
• Even if the run command is set to OFF, voltage is output to inverter output terminals U, V, and W if
the servo-lock command is ON.
• Even if the motor is stopped due to DC braking or preliminary excitation, voltage is output to inverter
output terminals U, V, and W.
An electric shock may occur.
• The inverter can easily accept high-speed operation. When changing the speed setting, carefully
check the specifications of motors or equipment beforehand.
Otherwise, injuries could occur.