4-56
Data for
F31/F35
[FM1]/[FM2] output
Function
(Monitor the following)
Meter scale
(Full scale at 100%)
8
PG feedback value
(speed)
Speed detected through the PG
interface, or estimated speed under
vector control without speed sensor
Maximum speed as 100%
9
DC link bus voltage
DC link bus voltage of the inverter
500 V for 230 V series,
1000 V for 460 V series
10
Universal AO
Command via communications link
(Refer to the RS-485 Communication
User's Manual.)
20000 as 100%
13
Motor output
Motor output (kW)
Twice the rated motor output
14
Calibration (+)
Full scale output of the meter
calibration
This always outputs the full-scale
(100%).
15
PID command (SV)
Command value under PID control
100% of the feedback amount
16
PID output (MV)
Output level of the PID controller
under PID control (Frequency
command)
Maximum frequency (F03)
17
Positional deviation in
synchronous running
Deviation in angle
0% to 50% to 100%,
representing -180° to 0° to +180°
of the deviation
If F31/F35 = 16 (PID output), J01 = 3 (Dancer control), and J62 = 2 or 3 (Ratio compensation enabled),
the PID output is equivalent to the ratio against the primary reference frequency and may vary within
300% of the frequency. The monitor displays the PID output in a converted absolute value. To indicate
the value up to the full-scale of 300%, set F30/F34 data to "33" (%).
F37
Load Selection/ Auto Torque Boost/ Auto Energy Saving Operation 1
F09 (Torque Boost 1)
H67 (Auto Energy Saving Operation (Mode selection)
F37 specifies V/f pattern, torque boost type, and auto energy saving operation in accordance with the
characteristics of the load.
Specify the torque boost level with F09 in order to assure sufficient starting torque.
Data for F37
V/f pattern
Torque boost
Auto energy
saving
Applicable load
0
Variable
torque V/f
pattern
Torque boost
specified by F09
Disable
Variable torque load
(General-purpose fans and
pumps)
1
Linear
V/f pattern
Constant torque load
2
Auto torque boost
Constant torque load
(To be selected if a motor may be
over-excited at no load.)
3
Variable
torque V/f
pattern
Torque boost
specified by F09
Enable
Variable torque load
(General-purpose fans and
pumps)
4
Linear
V/f pattern
Constant torque load
5
Auto torque boost
Constant torque load
(To be selected if a motor may be
over-excited at no load.)
If a required "load acceleration toque" is more than 50% of the constant torque, it is recommended
to select the linear V/f pattern (factory default).
• Under the vector control with speed sensor, F37 is used to specify whether the auto energy saving
operation is enabled or disabled. (V/f pattern and torque boost are disabled.)
Data for F37
Operation
0 to 2
Auto energy saving operation OFF
3 to 5
Auto energy saving operation ON
• Under the vector control without speed sensor, both F37 and F09 are disabled. The auto energy saving
operation is also disabled.