4-106
Multi-frequency 1 to 15 (C05 through C19
)
Data setting range: 0.00 to 500.00 (Hz)
The combination of
SS1
,
SS2
,
SS4
and
SS8
and the selected frequencies are as follows.
SS8
SS4
SS2
SS1
Selected frequency command
OFF
OFF
OFF
OFF
Other than multi-frequency *
OFF
OFF
OFF
ON
C05 (multi-frequency 1)
OFF
OFF
ON
OFF
C06 (multi-frequency 2)
OFF
OFF
ON
ON
C07 (multi-frequency 3)
OFF
ON
OFF
OFF
C08 (multi-frequency 4)
OFF
ON
OFF
ON
C09 (multi-frequency 5)
OFF
ON
ON
OFF
C10 (multi-frequency 6)
OFF
ON
ON
ON
C11 (multi-frequency 7)
ON
OFF
OFF
OFF
C12 (multi-frequency 8)
ON
OFF
OFF
ON
C13 (multi-frequency 9)
ON
OFF
ON
OFF
C14 (multi-frequency 10)
ON
OFF
ON
ON
C15 (multi-frequency 11)
ON
ON
OFF
OFF
C16 (multi-frequency 12)
ON
ON
OFF
ON
C17 (multi-frequency 13)
ON
ON
ON
OFF
C18 (multi-frequency 14)
ON
ON
ON
ON
C19 (multi-frequency 15)
* "Other than multi-frequency" includes frequency command 1 (F01), frequency command 2 (C30) and other
command sources except multi-frequency commands.
Note:
SS1, SS2, SS4 and SS8 are assigned to input terminals by parameters E01 through E07.
When enabling PID control (J01 = 1, 2, or 3)
Under the PID control, a multi-frequency command can be specified as a preset value (3 different frequencies). It
can also be used for a manual speed command even with the PID control being canceled (
Hz
/
PID
= ON) or for a
primary reference frequency under the PID dancer control.
• PID command
SS8
SS4
SS1, SS2
Command
OFF
OFF
–
Command specified by J02
OFF
ON
–
Multi-frequency by C08
ON
OFF
–
Multi-frequency by C12
ON
ON
–
Multi-frequency by C16
C08, C12, and C16 can be specified in increments of 1 Hz. The following gives the conversion formula between
the PID command value and the data to be specified.
Data to be specified = PID command (%)
Maximum frequency (F03)
100
PID command (%) =
Data to be specified (C08, C12, C16)
100
Maximum frequency (F03)
• Manual speed command
SS8, SS4
SS2
SS1
Selected frequency command
–
OFF
OFF
Other than multi-frequency
–
OFF
ON
C05 (Multi-frequency 1)
–
ON
OFF
C06 (Multi-frequency 2)
–
ON
ON
C07 (Multi-frequency 3)
Содержание EQ7 Series
Страница 1: ......
Страница 29: ...2 6 Unit inch mm Refer to Section 2 3 3 9 ...
Страница 94: ...4 25 Table B Motor Parameters Continued Three phase 460 V series EQ7 4_ _ _ C ...
Страница 152: ...4 83 Examples of Sequence Circuits 1 Standard sequence 2 Sequence with an emergency switching function ...