11-4
CT mode designed for constant torque load applications
Item
Specifications
Model EQ7-4XXX-C
125
150
200
250
300
350
450
500
600
700
800
900 1000
-
-
*1
Nominal applied motor
for
three
phase input [HP]
100
125
150
200
250
300
350
400
450
500
600
800
900
-
-
*1
Nominal applied motor
for
single
phase input [HP]
40
50
60
60
75
100
100
125
150
150
200
250
300
-
-
Ou
tp
ut
r
at
in
gs
Three
phase
input
Rated capacity
*2
[kVA]
120
140
167
202
242
300
330
414
466
518
590
765
932
-
-
Rated current [A]
150
176
210
253
304
377
415
520
585
650
740
960 1170
-
-
Single
phase
input
Rated capacity
*2
[kVA]
48
57
68
82
97
118
133
162
184
206
236
305
373
-
-
Rated current [A]
61
72
86
103
122
149
167
204
231
259
297
384
469
-
-
Rated voltage
*3
[V]
Three-phase, 380 to 480 V (with AVR function)
Overload capability
150%-1 min, 200% -3.0 s
Input
r
at
in
gs
Three
phase
input
Voltage, frequency
Three-phase, 380 to 440 V, 50 Hz
Three-phase, 380 to 480 V, 60 Hz
Voltage, frequency
variations
Voltage: +10 to -15% (Interphase voltage unbalance: 2% or less)
*4
, Frequency: +5 to -5%
Input current with
DCR
120
143
176
207
250
311
340
436
487
547
614
767
970
-
-
Required capacity
with DCR
*5
[kVA]
96
114
140
165
199
248
271
347
388
436
489
611
773
-
-
Single
phase
input
Voltage, frequency
Single-phase, 380 to 440 V, 50 Hz
Single-phase, 380 to 480 V, 60 Hz
Voltage, frequency
variations
Voltage: +10 to -10% , Frequency: +5 to -5%
Input current with
DCR
113
137
164
192
234
286
319
395
446
512
575
707
892
-
-
Required capacity
with DCR
*5
[kVA]
53
63
76
89
108
132
147
182
206
236
265
325
410
-
-
B
ra
kin
g
Torque
*6
[%]
10 to 15 %
Braking transistor
-
-
DC reactor (DCR)
As standard *7
Keypad
Multi-function keypad as standard
Applicable safety standards
UL508C, C22.2No.14, EN61800-5-1:2007,EN61800-5-2:2007 SIL2,
EN ISO13849-1:2008 PL=d Cat.3,EN954-1:1996 Cat.3
Enclosure (IEC60529)
IP00, UL open type , NEMA1(Option)
Cooling method
Fan cooling
Weight/Mass [lbs(kg)]
93
(42)
137
(62)
141
(64)
207
(94)
216
(98)
284
(129)
309
(140)
540
(245)
540
(245)
805
(365)
805
(365)
1170
(530)
1170
(530)
-
-
(*1) 4-pole standard motor
(*2) Rated capacity is calculated by assuming the output rated voltage as 230 V for 230 V series and 460 V for 460 V series.
(*3) Output voltage cannot exceed the power supply voltage.
At single-phase input use, the output voltage may be lower than three-phase input.
(*4) Voltage unbalance [%] = (Max. voltage [V] - Min. voltage [V])/Three-phase average voltage [V]×67(See IEC61800-3.)If this value is 2 to 3%, use an optional AC reactor (ACR).
(*5) Required when a DC reactor (DCR) is used.
(*6) Without external braking resistor condition. Average braking torque for the motor running alone. (It varies with the efficiency of the motor.)
(*7) For inverters of 100HP or above, the DC reactor is provided as separate standard component. Be sure to connect it to those inverters.
Содержание EQ7 Series
Страница 1: ......
Страница 29: ...2 6 Unit inch mm Refer to Section 2 3 3 9 ...
Страница 94: ...4 25 Table B Motor Parameters Continued Three phase 460 V series EQ7 4_ _ _ C ...
Страница 152: ...4 83 Examples of Sequence Circuits 1 Standard sequence 2 Sequence with an emergency switching function ...