89
Fault
name
Explanation
Fault
severity
Measures
Volt shift
Var adj
The reactive
power of the
inverter is
adjusted
according to the
change of grid
voltage.
Warning
Tap "Set-parameters" -
>
"Running
parameter" -
>
"Q-adjust switch" on the
LCD, to check whether the "Q-adjust
switch" is in the "QU mode".
GFRT
Run
When a grid fault
occurs, the
inverter can ride
through the time
interval.
Warning
Check whether the grid voltage exceeds
the HVRT or LVRT threshold.
DC
breaker
flt/
DC
switch
abnormal
DC switches of
the inverter are
abnormal.
Minor
Refer to the measures for "Branch
breaker flt".
Check whether the DC switch is
connected.
I
leakage-
pro
The sampling
value of the AC
leakage currents
exceeds the
protective
threshold.
Major
1. Check whether the AC cables are
damaged.
2. If the LV side of the transformer is
connected in the Y type, ensure that the
neutral point is unconnected.
If the fault still exists, contact Sungrow Service.
If the following fault occurs, immediately contact Sungrow Service. (referred to as "Sungrow"
hereinafter).
Fault name
Explanation
Fault
severity
Measures
Carrier
synch flt
The transmission of
carrier communication
signals is abnormal.
Major
Contact Sungrow.
Drive board
fault
Interior drive board of
the inverter is faulty.
Major
Contact Sungrow.