40
Cable Requirements
•
The maximum cross-sectional area of the aluminum/copper cable is 400mm
2
/750Kcmil.
•
Fasten the wiring terminal with the bolts in the scope of delivery. And the torques are
shown in following table.
Bolt
Torque
M12×55
60~70N.m/531~619.5lbf.inch
Cable Connection Steps
Proceed as follows to connect the DC cables:
step 1
Make sure the switch upstream of the combiner box is in the OFF position.
step 2
Lead the cable into the wiring area through the inlet hole, and mark the cable polarity.
step 3
Strip the protective layer of the cable to expose the copper core of the wire with strippers.
step 4
Install the OT/DT terminal to the wire and crimp them with a crimping tool. Install a heat
shrink tubing to the terminal and heat it with a heat gun.
step 5 Connect the cable.
1
Select bolts matching with the cable lug.
2
Attach the cable lug to the DC connection copper bar.
If copper wires are used, connect the spare parts as described below: