16
The DC load break switches/AC circuit breakers can be used together with a
micro-motor. When there is the power supply on the AC side of the inverter, the
energy can be stored to the breaker through this motor. When there is no power
supply on the AC side of the inverter, manually store the energy through the
manual energy storage handle.
The operation steps are briefly described by taking the load break switches as an example.
•
Switch on
Press the Push ON button on the panel to switch on.
Before switching on, check if the energy storage state displayed on the panel is CHARGED
SPRING. If the state is DISCHARGED SPRING, store the energy manually by turning the
manual energy storage handle down until the breaker panel displays CHARGED SPRING.
After the breaker is switched on, the breaker panel displays CLOSED.
Never manually connect the AC circuit breaker when the AC side carries voltage.
•
Switch off
Press the Push OFF button on the breaker panel to switch off the breaker.
After the breaker is switched off, the breaker panel displays OPEN