35
If you have any problems in relation to the ground cable connection, contact the
related technical personnel in time. Any installations not following the standards
or the installation and alternation without permission may lead to safety incidents
or damage to the devices. Sungrow shall not be held liable for the damages
caused.
6.5
AC Connection
6.5.1 Safety Instructions
Electrical shock hazards!
•
Do not touch the live components.
•
Disconnect the AC switches and ensure all terminals are voltage-free.
•
The connections to the downstream devices must be carried out only after
receiving approval from the distribution utility as required by national and state
interconnection regulations.
Strictly follow all the instructions when connecting.
6.5.2 AC Cable Connection
Prerequisites
•
Check and ensure that the AC side of the inverter is disconnected.
•
Disconnect the load switch of the transformer with the dedicated operation bar, where
reference can be made to the user manual of the transformer.
•
Open the operation box of the transformer, and get the key to the HV cabinet door as
well as the bolts required for wiring.
•
Remove the protection jacket from the HV tube.
•
Check and ensure that the tube and copper bar in the wiring area of the HV cabinet are
intact without any deformation or cracks.