On site, determine the number of output cables and the wiring scheme according to actual
situation.
After wiring, reliably connect the cable connector to the grounding copper bar inside the
high-voltage room according to local standards and regulations, where the fastening torque
is 60~70N.m.
A
B
C
D
E
F
Copper bus
Cable lug
Bolt(M12)
Disc spring
washer
Flat washer
Nut
- - End