110
15 Appendix
15.1 System Parameter
Input (DC)
SG3425UD-MV
SG3600UD-MV
Max. PV input voltage
1500V
Min. PV input voltage
875 V
915V
Startup input voltage
915 V
955 V
Available DC fuse sizes
250A, 315A, 400A, 450A, 500A
MPP voltage range
875 ~ 1300 V
915 ~ 1300 V
No. of independent MPP inputs
1
No. of DC inputs
20 (optional: 22 / 24 / 26 / 28)
Max. DC short-circuit current
10000 A
PV array configuration
Negative grounding or floating
Output (AC)
AC output power
3425 kVA @ 45
℃
(113
℉
)
3083 kVA @ 50
℃
(122
℉
)
3600 kVA @ 45
℃
(113
℉
)
3240 kVA @ 50
℃
(122
℉
)
Nominal grid frequency
50 Hz / 60 Hz
Grid frequency range
45 ~55 Hz / 55 ~ 65 Hz
THD
< 3 % (at nominal power)
Power factor at nominal power
0.99
Adjustable power factor
0.8 leading ~0.8 lagging
Efficiency
Inverter Max. efficiency
98.9 %
Inverter Euro. efficiency
98.5 %
Transformer
Transformer rated power
3425 kVA
3600 kVA
Transformer max. power
3425 kVA
3600 kVA
LV / MV voltage
0.6 kV / (12 – 35) kV
0.63 kV / (12 – 35) kV
Transformer vector
Dy1 or Dy11
Transformer cooling type
ONAN (Optional: KNAN)
Protections & Functions
DC input protection
Load break fuse
Inverter output protection
Circuit breaker
AC MV output protection
Load break fuse
Overvoltage protection
DC Type II / AC Type II